Growatt MID 30KTL3-X - Troubleshooting; Error message; System error

Growatt MID 30KTL3-X
30 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
37
38
Warning
message
Description
Suggest
Warning 207
USB overcurrent
protection
1Unplug the U disk;
2.Reconnect the U disk after shutdown;
3.If the fault message still exists,contact the
manufacturer.
Warning 208
DC fuse is broken
1.Check the fuse after shutdown;
2.If the fault message still exists,contact the
manufacturer.
Warning 209
Panel voltage is too
high
1.Disconnect the DC switch immediately and
confirm the voltage;
2.fter the normal voltage is restored, if the fault
message still exists,contact the manufacturer.
Warning 210
Panel reverse
1.Check the panel input;
2.If the fault message still exists,contact the
manufacturer.
Warning 300
No mains connection
1.Please confirm whether the power grid is lost;
2.If the fault message still exists,contact the
manufacturer.
Warning 301
Mains voltage is out of
range
1.Check whether the AC voltage is within the
specification range of the standard voltage;
2.If the fault message still exists,contact the
manufacturer.
Warning 302
Mains frequency is out
of range
1.Check whether the frequency is within the
range;
2.If the fault message still exists, contact the
manufacturer.
Warning 303
Output overload
1.Reduce output power;
2.If the fault message still exists, contact the
manufacturer.
Warning 304
Open current
transformer
1.Check whether the current transformer is
connected well;
2.If the fault message still exists, contact the
manufacturer.
Warning 305
Reverse connection of
current transformer
1.Check whether the current transformer is
connected reversely;
2.If the fault message still exists,contact the
manufacturer.
Warning 306
Communication failure
of current transformer
1.Please check the communication line;
2.If the fault information still exists,contact the
manufacturer.
Warning 307
Wireless CT pairing
timeout
1.Please check the communication line;
2.If the fault information still exists,contact the
manufacturer.
Warning 400
Fan function is
abnormal
1.Check the fan wiring after shutdown;
2.Replace the fan;
3.If the fault information still exists,contact the
manufacturer.
Warning
message
Description
Suggest
Warning 401
The meter is abnormal
1.Check whether the meter is turned on;
2.Check whether the connection between the
machine and the meter is normal.
Warning 402
Optimizer and inverter
communication
abnormal
1.Check if the optimizer is open;
2.Check whether the connection between the
optimizer and the inverter is normal.
Warning 403
String communication
abnormal
1.Check the string board wiring after shutdown;
2.If the fault message still exists,contact the
manufacturer.
Warning 404
Memory exception
1.Restart the inverter;
2.If the fault message still exists, contact the
manufacturer.
Warning 405
The firmware version
of the control board
and the
communication board
do not match
1.Check the firmware version;
2.If the fault message still exists, contact the
manufacturer.
Warning 406
Boost circuit failure
1.Restart the inverter;
2.If the fault message still exists,contact the
manufacturer.