13.3 System error
Error code
Description
Suggest
Error 200
AFCI Fault
1.After shutdown,Check the panel terminal.
2.Restart inverter.
3.If error message still exists,contact manufacturer.
Error 201
Leakage c u r re nt
too high.
1.Restart inverter.
2.If error message still exists,contact manufacturer.
Error 202
The DC input
voltage is
exceeding the
maximum
tolerable value.
1.Immediately disconnect the DC switch and check the
voltage
2.If the fault code still exists after the normal voltage is
restored, contact manufacturer
Error 203
PV isolation Low
1.After shutdown, check whether the panel shell is
reliably grounded.
2.If error message still exists,contact manufacturer.
Error 300
AC V Outrange
1.Check grid voltage.
2.If the error message still exists despite the grid voltage
being within the tolerable range, contact
manufacturer.
Error 301
AC terminals
reversed
1.Check AC terminals
2.If error message still exists,contact manufacturer.
Error 302
No AC Connection
1.After shutdown,Check AC wiring.
2.If error message still exists,contact manufacturer.
Error 303
NE abnormal
1.Check PE,to ensure that the PE line contact good.
2.If error message still exisits,contact Manufacturer.
Error 304
AC F Outrange
1.Restart inverter.
2.If error message still exists,contact manufacturer.
Error 305
Over Load Fault
1.Check whether output load over range; If load too
large, please reduce load
2.If error message still exists, contact manufacturer.
Error 306
CT LN Reversed
1.After shutdown Check the SP-CT connection.
2.If error message still exists,contact manufacturer.
Error 307
C o m m u n i c a t i o n
f a u l t , M 3 d i d n ' t
receive SP-CT data
1.Check communication wire
2.If error message still exists,contact manufacturer.
Error 308
C o m m u n i c a t i o n
fault;Pairing time
too long
1.Restart pairing
2.If error message still exists,contact manufacturer.
Error code
Description
Suggest
Error 400
DCI bias abnormal
1.Restart inverter
2.If error message still exists, contact manufacturer.
Error 401
DC Voltage High
Fault
1.Restart inverter.
2.If error message still exists,contact manufacturer.
Error 402
Output DC current
too high.
1.Restart inverter.
2.If error message still exists,contact manufacturer.
Error 403
O u t p u t c u r r e n t
unbalance
1.After shutdown,Check the output current is not
balanced.
2. If the error message still exists, contact manufacturer
Error 404
bus sample fault
1.Restart inverter.
2.If error message still exists,contact manufacturer.
Error 405
Relay fault
1.Restart inverter.
2.If error message still exists,contact manufacturer.
Error 406
Init model fault
1.Reset mode
2.If error message still exists,contact manufacturer.
Error 407
AutoTest failure
1.Restart inverter.
2.If error message still exists,contact manufacturer.
Error 408
NTC Temperature
too high
1.After shutdown,Check the temperature, normal restart
the inverter
2. If the error message still exists, contact manufacturer
Error 409
Bus voltage
abnormal
1.Restart inverter.
2.If error message still exists,contact manufacturer.
Error 410
C o m m u n i c a t i o n
board and control
p a n e l s a m p l i n g
battery voltage is
inconsistent
1.Restart inverter
2.If error message still exists, contact manufacturer.
Error 411
Communication
fault
1.After shutdown,Check communication board wiring
2. If the error message still exists, contact manufacturer
Error 412
Temperature
sensor connection
is abnormal
1.After shutdown,Check the temperature sampling
module is connected properly
2.If the error message still exists, contact manufacturer

Other manuals for Growatt MOD 11KTL3-X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Growatt MOD 11KTL3-X and is the answer not in the manual?

Growatt MOD 11KTL3-X Specifications

General IconGeneral
Product type-
Maximum power11000 W
Output current18.3 A
Output frequency50/60 Hz
MPP voltage range140 - 1000 V
Number of strings per MPPT1
Output power capacity (max)11 kVA
Input operation voltage (max)1100 V
Input operation voltage (min)160 V
Maximum input current per MPPT13 A
Output operation voltage (max)440 V
Output operation voltage (min)340 V
Total Harmonic Distortion (THD)3 %
Number of maximum power point tracking (MPPT)2
Operating temperature (T-T)-25 - 60 °C
Built-in displayYes
Display technologyOLED
Product colorWhite
Overvoltage categoryCAT II
Power protection featuresOver voltage, Short circuit
International Protection (IP) codeIP66
Weight and Dimensions IconWeight and Dimensions
Depth178 mm
Width425 mm
Height387 mm

Related product manuals