Parallel Installation Guide
Introduction
This inverter can be used in parallel with three different operation modes.
1.
Parallel operation in single phase with up to 6 units.
2.
Maximum 6 units work together to support 3-phase output. 4 units support one phase maximum.
3.
Maximum 6 units work together to support split phase output. 5 units support one phase maximum.
NOTE: If the package includes share current cable and parallel cable, the inverter is default supported parallel
operation. You may skip section 3. If not, please purchase parallel kit and install this unit by following instruction
from professional technical personnel in local dealer.
Package Contents
In parallel kit, you will find the following items in the package:
Parallel board Parallel communication cable Current sharing cable
Parallel Board Installation
Step 1: Remove wire cover by unscrewing all screws.
Step 2: Remove WiFi/GPRS communication board and CAN/RS485 communication board by unscrewing screws as
below chart, and remove 2-pin and 6-pin cables.