22
chart 5.20
chart 5.21
Step 5:To remove the AC output terminal , press the bayonet out of the slot with a
small screwdriver and pull it out.
Step 3: Push threaded sleeve on to connection terminal until both are locked
tightly.
Step 4: Align the bayonet of the AC output terminal to the slot of thread sleeve,
Plug the socket into AC output terminal.
The recommended wiring diagram is as follows:
Chart 5.22
SPHInverter
ACGRID
L L
UPS OUTPUT
N N
E E
Sensor
L LN NE E
TSSP
Battery
L
N
PE
PV
UPS
21
Chart 5.23
Chart 5.24
Note: This diagram is an example for gird system without special requirement on
electrical wiring connection.
Note: This diagram is an example for Australian and New Zealand gird system where
neutral line can't be switched.
SPHInverter
ACGRID
L L
UPS OUTPUT
N N
E E
Sensor
L LN NE E
TSSP
Battery
L
N
PE
PV
UPS
Note: This diagram is an example for customer who only want to use the on grid
system .