7.1 PROFINET technical specifications
Functionality PROFINET RT
• PROFINET device according to Conformance Class B
•
Media Redundancy Protocol (MRP) Client
• System redundancy S2
• Multicast provider and subscriber
Minimum cycle time PROFINET RT 250 μs
Number of IO connections per controller
2 for cyclic data
1 for parameter set
Maximum number of IO data 1024 bytes
GSDML version V2.34
Dynamic IO configuration Supported
Diagnostics Supported
Maximum number of data modules 85
Watchdog
Communication watchdog with fixed 2 seconds time-out. It
can be enabled via the control module in the device
profile.
Certificate Conformance July 2019
22
English (GB)