9.4 Cellular network Real Time Clock
9.5 Control register block
Registers in this block can be read by means of function codes
0x03 and/or 0x04. They can be written as holding registers with
function codes 0x06 and 0x10.
1 For Multi-E with a module in the master pump, only set the
master pump CopyToLocal bit to value "1".
For Multi-E with a module in two pumps, always set
CopyToLocal reg. 00101 bit 4 to value "1" in both pumps. Any
writings to the control registers 00101, 00102, 00103 and
00104 must be written to each pump.
A TPED model H is essentially a Multi-E model H with two
pumps. If a CIM module is mounted in each pump head,
always set CopyToLocal bit to value "1" in both pump heads.
Any writings to control bits and registers must be written to
each pump head.
2
If pump 2 also has a CIM mounted (for redundancy), any
writings to control bits and registers must be written for each
pump head.
00029
GeneralStatus
Bit 0: ScadaPinCodeEnabled
PIN code functionality.
0: No PIN code required
1: PIN code required to perform remote control and configuration.
Activation of SCADA PIn-code protection takes place via the SMS
command "SCADACODE". See "CIM 260 SMS commands", which you
can download from Grundfos Product Center.
-●-
GeneralStatus
Bit 1: WriteAccess
Remote write access.
0: No write access, the PIN code is incorrect.
1: Full write access, the PIN code is either correct or not enabled.
00030 UnitFamily Grundfos product family.
00031 UnitType Grundfos product type.
00032 UnitVersion Grundfos product version.
00033 BatteryState
State of CIM 260 module battery
0: Battery not present
1: Battery must be replaced
2: Battery charging
3: Battery needs charging, but temperature too high
4: Battery needs charging, but temperature too low
5: Battery low
6: Battery OK
255: Battery state not available
-●-
00034 ProductSoftwareVersionHI Product software version - BCD digit 1-4 aa.bb
00035 ProductSoftwareVersionLO Product software version - BCD digit 5-8 cc.dd
00036 ProductSoftwareDayMonth Product software date - BCD ddmm
00037 ProductSoftwareYear Product software date - BCD yyyy
Address Register name Description
CIM
200
CIM
260
CIM
500
00080 SetUNIXRealTimeClockHI
Set real time clock (32 bit UNIX format)
Triggered on value change
-●-
00081 SetUNIXRealTimeClockLO -●-
00082 SetRtcSecond Set real time clock - seconds - -
00083 SetRtcMinute Set real time clock - minutes - -
00084 SetRtcHour Set real time clock - hours - -
00085 SetRtcDay Set real time clock - day - -
00086 SetRtcMonth Set real time clock - month - -
00087 SetRtcYear Set real time clock - year - -
00088 Bit 0: SetRtc Triggers setting of real time clock - s/m/h/d/m/y format - -
00089 StatusUNIXRealTimeClockHI
Real time clock (32 bit UNIX format)
-●-
00090 StatusUNIXRealTimeClockLO -●-
00091 StatusRtcSecond Real time clock - seconds - -
00092 StatusRtcMinute Real time clock - minutes - -
00093 StatusRtcHour Real time clock - hours - -
00094 StatusRtcDay Real time clock - day of month - -
00095 StatusRtcMonth Real time clock - month - -
00096 StatusRtcYear Real time clock - year (after 2000) - -
00097 Bit 0: StatusSetRTCAck Acknowledge of set RTC command - -
Address Register name Description
CIM
200
CIM
260
CIM
500