EasyManua.ls Logo

Grundfos CIU 200 - Control Modes; 10 Detailed Descriptions of Functionality

Grundfos CIU 200
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
English (GB)
35
10. Detailed descriptions of functionality
10.1 Control modes
The supported control modes are described further in this section.
H: Pressure (Head)
Q: Flow
Control modes Description Illustration
> Constant speed (0)
> Constant frequency (1)
Open loop:
The setpoint of the booster is interpreted as the setpoint for
the performance.
The setpoint value is a percentage of the maximum
performance of the booster.
No sensor is required in these modes.
TM04 2289 2208
> Constant head (3)
> Constant pressure (4)
> Constant differential pressure (5)
Closed loop:
The setpoint of the booster is interpreted as the setpoint for
the pressure.
The booster adapts the speed so that the pressure is
constant, regardless of the flow.
A pressure sensor is required.
TM04 2290 2208
> Constant flow (7)
> Constant temperature (8)
> Constant level (10)
Closed loop:
The setpoint of the booster is interpreted as the setpoint for
the flow, temperature or level. Constant flow is indicated in
the diagram.
A relevant sensor is required:
A flow sensor for flow control
a temperature sensor for temperature control
a level sensor for level control.
TM04 2288 2208
> Proportional pressure (6)
Closed loop:
The setpoint of the booster system is interpreted as a
proportional-pressure setpoint as shown in the fig. A
pressure sensor is required.
TM04 2291 2208
> DDD AUTO
ADAPT
(128)
The setpoint of the DDD system is interpreted as a
proportional-pressure setpoint as shown in the figure. The
proportional curve is adjusted automatically once a day
according to remote DDD sensor data.
TM05 3241 1012
> FLOW
ADAPT
(129)
This control mode works similar to AUTO
ADAPT
, except that
the flow-limiting function, FLOW
LIMIT
, is always active and
limits the flow to the value ActualMaxFlowLimit.
TM05 3242 1012
> Closed-loop sensor (130)
This is a general purpose closed-loop control mode that
you can use in cases where the pump is used for a type of
control not covered by one of the other control modes.
H
Q
H
Q
H
Q
H
Q
Q
H
H
Q

Table of Contents

Other manuals for Grundfos CIU 200

Related product manuals