EasyManua.ls Logo

Grundfos DDI Series

Grundfos DDI Series
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3
5.1.3 PROFIBUS cable
The bus cable installed is too long or the transmission speed
is too high.
Incorrect cable type installed (not a PROFIBUS cable).
Cables from different manufacturers installed.
The branch lines are too long.
The minimum cable length of 1 metre between the devices on
the bus has not been observed.
5.1.4 Electrical environment
No or insufficient equipotential bonding conductors.
Insufficient signal level on the RS-485 line.
Electromagnetic interference problems:
– capacitive coupling
– discharges
– leakage currents on screened cables
– potential sources of interference, such as frequency
converters, contactors, motors, etc.
– PROFIBUS cable installed too close to potential sources of
interference.
Incorrect power supply concept.
Unsuitable earthing concept.
Screened cable not earthed on both sides. Earthing does not
cover a sufficiently large area.
5.1.5 Bus settings
No master in the system.
Bus option not set to "on".
Incorrect bus address set.
Bus address assigned more than once.
Incorrect baud rate set for the master.
Too many devices (more than 32) in a single bus segment.
5.2 Connection to the DDI pump
Fig. 1 Connection to DDI 209
Fig. 2 Connection to DDI 222
For the PROFIBUS-DP, attach a Y-M12 connector to socket 6
of the pump.
Connect the bus to the sockets of the Y-M12 connector using
2-pin PROFIBUS cables.
5.2.1 Pin assignment, socket 6
5.2.2 Bus connection
If the pump is the last device on the bus, it must be equipped with
a bus terminal resistor.
Screw the bus terminal resistor onto the Y-M12 plug.
5.3 Accessories: connector for PROFIBUS-DP
Fig. 3 Connector for PROFIBUS-DP
5.4 Installation diagram with terminal resistor
Fig. 4 Installation diagram
Note
For additional information, please refer to the
PROFIBUS Guidelines (PROFIBUS-DP/FMS
Installation Guidelines, Order No. 2.111) from the
Profibus User Organisation (www.profibus.com).
TM03 6582 4506
6
1
2
3
4
5
TM03 6583 4506
Socket 6
Used for
Pin Assignment
1 + 5 V Bus terminal resistors
2 RxD/TxD-N Received/sent data (line A)
3GND
4 RxD/TxD-P Received/sent data (line B)
5 Screen/protective earth
Note
To ensure the fault tolerance of the PROFIBUS
system in the event of a device fault or when a
device is replaced, a separate active bus terminal
resistor is recommended.
TM03 6584 4506TM03 6585 4506
1
3
5
42
1
2
3
4
5
6
1
2
3
4
optional
5
1
2
3
4
2
1
4
3
1
2
3
4
5
1
2
4
3

Related product manuals