EasyManua.ls Logo

Grundfos DDI Series

Grundfos DDI Series
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8
6.4 Data transmission (programming examples)
Example 1
The pump is to be switched on and off via PROFIBUS. The
setpoint (volume flow) and the operating mode are set on the
pump.
PROFIBUS settings
for switching on the pump
– byte 1 = 00h
– byte 2 = 01h – set bit 0, switch on the pump
– byte 3 = 00h
– byte 4 = 00h.
for switching off the pump
– byte 1 = 00h
– byte 2 = 00h
– byte 3 = 00h
– byte 4 = 00h.
Example 2
The pump is to be switched on and off via PROFIBUS. The
setpoint is 1 l/h and is transferred via PROFIBUS. The pump is to
be operated in slow mode.
PROFIBUS settings
for transferring the setpoint
– byte 1 = 20 – set bit 5, accept setpoint
– byte 2 = 00h
– byte 3 = 03h – setpoint 1000 ml/h (decimal)
– byte 4 = E8h – corresponds to 03E8 in hexadecimal format.
The transferred setpoint can be read and monitored via the
feedback actual value for bytes 1 and 2.
for switching on the pump and slow mode:
– byte 1 = 00h
– byte 2 = 03h – set bits 0 and 1, switch on pump and slow
mode
– byte 3 = 00h
– byte 4 = 00h.
7. Disposal
This product or parts of it must be disposed of in an
environmentally sound way:
1. Use appropriate waste collection services.
2. If this is not possible, contact the nearest Grundfos or
Grundfos Alldos company or service workshop.
Subject to alterations.

Related product manuals