EasyManua.ls Logo

Grundfos DDI Series

Grundfos DDI Series
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
Setting and executing additional control functions
Remote on/off (byte 2/bit 0)
– Switches the pump on and off. For switching on, the pump
must not have been manually stopped or switched off via
external remote on/off. External remote off and switching off
via PROFIBUS switch the pump off independently of each
other.
Slow mode (byte 2/bit 1)
– Slow-mode operation is switched on and off.
Continuous operation for deaeration and suction (byte 2/bit 2)
Deletion (resetting) of the total capacity dosed (byte 2/bit 3)
– The display of the total capacity dosed (since the pump was
last reset) is reset to zero.
Error resetting (byte 2/bit 4)
– Resetting of an error that has occurred and restarting of the
pump if it was set to "Start" locally.
Dosing controller (byte 2/bit 5)
– An installed Flow Monitor can be switched on and off.
6.3.2 Messages returned from the pump
Data flow from the pump to the PROFIBUS master
8 bytes are available for returning messages from the pump:
The following data is sent from the pump to the PROFIBUS
master via PROFIBUS-DP:
Actual value: volume flow (ml/h) / chamber pressure (mbar)
(bytes 1, 2)
– The set setpoint is determined if "Transfer of actual value" is
set to "Volume flow" (DDI 209 in ml/h, DDI 222 in cl/h).
The chamber pressure in mbar is transferred when
"Pressure value" is set and "Pressure control" is activated.
Display of the total capacity dosed (bytes 3, 4)
– Display of the total capacity dosed in dl (decilitres) since the
value was last reset.
Error messages (bytes 5, 6/bits 15-0)
– dosing controller
– diaphragm leakage detection
– external pre-empty signal
– empty signal
– Hall sensor (for motor monitoring)
– PROFIBUS communication
– current control – for operating mode "manual" 4-20 mA.
An error message is sent if the current input is < 2 mA.
Bit
Byte 2:
Control functions for
DDI 209
Byte 2:
Control functions for
DDI 222
0
Remote on/off
0 = off
1 = on
Remote on/off
0 = off
1 = on
1
Slow mode
0 = off
1 = on
Slow mode 1
0 = off
1 = on
2
Continuous operation
(deaeration mode)
0 = off
1 = on
Continuous operation
(deaeration mode)
0 = off
1 = on
3
Deletion (resetting) of the
total capacity dosed
0 -> 1 = Resets the total
capacity dosed
Deletion (resetting) of the
total capacity dosed
0 -> 1 = Resets the total
capacity dosed
4
Error resetting 0 -> 1 =
Resets the error
Error resetting 0 -> 1 =
Resets the error
5
Flow
0 = off
1 = on
Flow
0 = off
1 = on
6 Reserve Slow mode 2
7
Pressure monitoring, only
with Flow Monitor option
0 = on
1 = off
Pressure monitoring
0 = on
1 = off
Byte Data type Data length [byte]
1, 2
Unsigned 16
Highbyte, Lowbyte
2
3, 4
Unsigned 16
Highbyte, Lowbyte
2
5, 6 Unsigned 16 2
7, 8 Byte 2
Bit Bytes 5, 6: Error messages
0
Dosing controller
0 = no error
1 = error
1
Diaphragm leakage detection (MLS)
0 = no error
1 = error
2
Pre-empty signal
0 = no error
1 = error
3
Empty signal
0 = no error
1 = error
4
Hall sensor (for motor monitoring)
0 = no error
1 = error
5
PROFIBUS communication (inverse)
0 = error
1 = no error
6
Current control
(< 2 mA in operating mode 4-20 mA)
0 = no error
1 = error
7, 8 Reserve
9
Internal pre-empty signal
0 = no error
1 = error
10 Reserve
11
Only for DDI 209 with Flow Monitor and DDI 222:
If the pressure is exceeded 5 times (starting can be
initiated after 10 minutes)
0 = no error
1 = error
12
Only for DDI 209 with Flow Monitor and DDI 222:
If the pressure is exceeded 1-5 times in succession
0 = no error
1 = error
13-15 Reserve

Related product manuals