8. Fit the coupling guard. Tighten the screws to the
correct torque. See below.
M5 x 10 mm: 6 ± 2 Nm
TM033919
4.2 Location
CAUTION
Hot or cold surface
Minor or moderate personal injury
When pumping hot or cold liquids,
make sure that no one can accidentally
come into contact with hot or cold
surfaces.
The pump must be sited in a well-ventilated, but frost-
free location.
4.2.1 Vertical installation, NB, NBG
For inspection and repair, allow suitable
clearances for pump or motor removal.
Pumps fitted with motors up to and including 4 kW
require a 0.3 m clearance above the motor.
Pumps fitted with motors of 5.5 kW and up require
at least a 1 m clearance above the motor to allow
the use of lifting equipment.
A
TM034128
Clearance above the motor
Motor Minimum clearance, A
0.25 - 4 kW 0.3 m
5.5 - 37 kW 1 m
18
English (GB)