6. Fault finding
6.1 Fault codes and remedies
Fault
code
Fault
ID
Fault name Possible cause Remedy
1
1
Overcurrent
(hardware fault)
AC drive has detected too high a
current (> 4*I
H
) in the motor cable:
sudden heavy load increase
short circuit in motor cables
unsuitable motor
Check loading.
Check motor.
Check cables and connections.
Make identification run.
Check ramp times.
2
Overcurrent
(software fault)
2
10
Overvoltage
(hardware fault)
The DC-link voltage has exceeded
the limits defined.
too short a deceleration time
brake chopper is disabled
high overvoltage spikes in supply
Start/Stop sequence too fast
Make deceleration time longer.
Use brake chopper or brake
resistor (available as options).
Activate overvoltage controller.
Check input voltage.
11
Overvoltage
(software fault)
3
20
Earth fault
(hardware fault)
Current measurement has detected
that the sum of motor phase current
is not zero.
insulation failure in cables or
motor
Check motor cables and motor.
21
Earth fault
(software fault)
540Charging switch
The charging switch is open, when
the START command has been
given.
faulty operation
component failure
Reset the fault and restart.
Should the fault re-occur,
contact the distributor near to
you.
760Saturation
Various causes:
defective component
brake resistor short-circuit or
overload
Cannot be reset from keypad.
Switch off power.
Do not re-connect power!
Contact factory.
If this fault appears
simultaneously with F1, check
motor cables and motor.