7
4. Installation
4.1 Installation example
Fig. 4 Installation example showing the required clearance when mounting the product
Warning
Installation must be carried out by qualified
staff.
Caution
You must adjust the minimum frequency to
a value that ensures water is discharged
from the outlet of the pump
Note
To adjust the min Frequency click the
home button on the control panel and
select min Frequency
Caution
To ensure a good convective cooling
effect, install the inverter vertically with at
least 10 cm free space at the top and
bottom.
To be installed indoors. Do not install the
equipment in direct sunlight.
Caution
Please ensure that the mounting wall can
support the weight of the inverter. Find
weight in 3.2 Technical data.
TM06 6529 1813
A
C B
A
Type A
B C
сůĞĂƌĂŶĐĞůĞŌĂŶĚƌŝŐŚƚĨƌŽŵƚŚĞĚƌŝǀĞ
сůĞĂƌĂŶĐĞĂďŽǀĞƚŚĞĚƌŝǀĞ
сůĞĂƌĂŶĐĞůƵŶĚĞƌŶĞĂƚŚƚŚĞĚƌŝǀĞĚƌŝǀĞ
80 160 60
DŝŶĐůĞĂƌĂŶĐĞ΀ŵŵ΁
ůůƚLJƉĞƐ
100X
T
A = Clearance left and right from the drive
B = Clearance above the drive
C = Clearance underneath the AC drive
Min clearance
[mm]
Type A B C
All types 80 160 60