English (GB)
22
Fig. 14 Start and stop levels
Make sure that the effective volume of the pit does
not become so low that the number of starts per hour
exceeds the maximum permissible number. See
section 10. Technical data.
7.2.3 IO 113
IO 113 provides an interface between a Grundfos
wastewater pump equipped with sensors and the
pump controller(s). The most important sensor status
information is indicated on the front cover.
One pump can be connected to one IO 113. Together
with the sensors, IO 113 provides a galvanic isolation
between the motor voltage in the pump and the
connected controller(s).
IO 113 can do the following, as standard:
• protect the pump against overheating
• monitor the status of these items:
– motor winding temperature
– leakage (WIO or WIA)
– moisture in the pump
• measure the stator insulation resistance
• stop the pump in case of alarm
• remotely monitor the pump via RS-485
communication (Modbus or GENIbus)
• control the pump via a frequency converter.
Fig. 15 IO 113
TM06 5988 0216
Do not use IO 113 for other purposes than
those mentioned in the installation and
operating instructions for IO 113.
TM05 1881 3811
Pos. Description
1 Terminals for alarm relay
2
Terminals for analog and digital inputs
and outputs
3 Terminals for supply voltage
4
Potentiometer for setting the warning limit
of stator insulation resistance
5
Terminals for RS-485 for GENIbus or
Modbus
6 Indicator light for moisture measurement
7
Indicator light for stator insulation
resistance
8 Indicator light for leakage (WIO or WIA)
9 Indicator light for vibrations in the pump
10
Terminals for measurement of stator
insulation resistance
11 Terminals for connection of pump sensors
12 DIP switch for configuration
13 Indicator light for motor temperature
14 Button for resetting alarms
15 Indicator light for motor running
16 Indicator light for service
17 Terminals for digital outputs
PET1 T2
G1 A1 G2 A2 K1 K2 R1 R2
D1 D2 D3 D4 D5 D6 D7 D8
P1 P2 P3 P4 P5
AYB
I1 I2 I3
ON DIP
12345678910
11 1 2
12 3
4
5
6
7
8
9
1011