3.4 Configuration examples
Fig. 7 Configuration from factory
Figure 7 shows the factory configuration (jumpers are shown as light grey
rectangles): The supply voltage is set to 230 VAC (possibly 24 VDC), both
sensor inputs are set to 0.5 - 3.5 V, and both signal outputs to 4-20 mA.
TM04 5048 2509
1
2
3
1
2
3
1
2
3
1
2
3
ST1
ST2
ST3
ST4
LH H L
U1
I
ST1: Ch1 out - I=4-20mA ; U1=2-10V; U2=1-5V
ST2: Ch2 out - I=4-20mA ; U1=2-10V; U2=1-5V
ST3: Ch1 input voltage span; L=0.5-3.5; H=0.5-4,5
ST4: Ch1 input voltage span; L=0.5-3.5; H=0.5-4,5