English (GB)
9
Fig. 5 ST3 (input 1) is configured for sensors giving an 0.5 - 3.5 V signal,
ST4 (input 2) is configured for sensors giving an 0.5 - 4.5 V signal
3.3 ST1 and ST2 - signal outputs
Fig. 6 ST1 (output 1) is set to 2-10 V, and ST2 (output 2) to 1-5 V
TM04 4888 2206
Short-circuit
position
Location
(see fig. 7)
Function
ST1
I
Output 1, output current 4-20 mA (factory setting)
U1 Output 1, output voltage 2-10 V
U2 Output 1, output voltage 1-5 V
ST2
I
Output 2, output current 4-20 mA (factory setting)
U1 Output 2, output voltage 2-10 V
U2 Output 2, output voltage 1-5 V
TM04 4887 2209