EasyManua.ls Logo

Grundfos SI 010 CNV - ST3 and ST4 - Sensor Inputs; ST5 - Supply Voltage

Grundfos SI 010 CNV
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
English (GB)
8
3.1 ST5 - supply voltage
In position ST5, SI 010 CNV can be set to either 230 V or 115 V supply
voltage:
one jumper across the two pins in the middle = 230 V.
two jumpers as shown in fig. 4 = 115 V.
If the converter is connected to 24 VDC, the configuration of ST5 has no
function.
Fig. 4 How to set SI 010 CNV to 230 V and 115 V
3.2 ST3 and ST4 - sensor inputs
The sensors are available in two versions with different output signals, either
0.5 - 3.5 V or 0.5 - 4.5 V. The converter is compatible with both signal types
which are configured in short-circuit positions ST3 and ST4.
Caution
The SI 010 CNV can be connected to either 230/115 VAC or
24 VDC. It must NOT be connected to both voltages.
TM04 4885 2209, TM04 4886 2209
Short-circuit
position
Location
(see fig. 7)
Function
ST3
L
Input 1, input voltage 0.5 - 3.5 V
(factory setting)
H Input 1, input voltage 0.5 - 4.5 V
ST4
L
Input 2, input voltage 0.5 - 3.5 V
(factory setting)
H Input 2, input voltage 0.5 - 4.5 V
Set to 230 V (factory setting)
Set to 115 V