EasyManua.ls Logo

Haes Excel-EN - Dependency Modes (False Alarm Management)

Default Icon
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
36
SETUP & PROGRAMMING
DEPENDENCY MODES (FALSE ALARM MANAGEMENT)
Dependency modes are features described in EN54-2 for the processing of con rmation alarms. It is a
requirement by some monitoring stations and local re authoities in order to reduce the possibility of false
alarms.
The panel has 3 dependency mode options, A, B & C. Only one type can be applied to the panel but any
or all zones can be independently set for dependency mode.
Dependency mode, if assigned to a zone, is set to type A by default.
Dependency ‘A’ will apply the following sequence:
1.
1.
The rst detector alarm is inhibited.
The rst detector alarm is inhibited.
2.
2.
The panel resets and re-checks the inhibited zone within 15-30 seconds.
The panel resets and re-checks the inhibited zone within 15-30 seconds.
3.
3.
If an alarm is detected then the panel activates a full re condition.
If an alarm is detected then the panel activates a full re condition.
4.
4.
If no alarm is detected, the panel stays in an alert condition for 30 minutes. Any new alarm from
If no alarm is detected, the panel stays in an alert condition for 30 minutes. Any new alarm from
the same zone within this time activates a full re condition.
the same zone within this time activates a full re condition.
5.
5.
After 30 minutes or if RESET, the panel reverts to step 1.
After 30 minutes or if RESET, the panel reverts to step 1.
Note: 220Ω ‘Evacuate’ call points should be used on such zones to provide an instant un-delayed alarm.
A 470Ω call point will be included in the dependency delay sequence.
Dependency ‘B’ will apply the following sequence:
1.
1.
The rst detector alarm will indicate at the control panel but not activate the sounders.
The rst detector alarm will indicate at the control panel but not activate the sounders.
2.
2.
The panel resets and re-checks the inhibited zone within 1 - 4 minutes (programmable, see code
The panel resets and re-checks the inhibited zone within 1 - 4 minutes (programmable, see code
2-1-3-4)
2-1-3-4)
1
1
.
.
3.
3.
If an alarm is detected then the panel activates a full re condition.
If an alarm is detected then the panel activates a full re condition.
4.
4.
If no alarm is detected, the panel stays in an alert condition for 5 - 30 minutes (programmable,
If no alarm is detected, the panel stays in an alert condition for 5 - 30 minutes (programmable,
see code 2-1-3-4)
see code 2-1-3-4)
2
2
. Any new alarm from the same or a different zone within this time activates a
. Any new alarm from the same or a different zone within this time activates a
full re condition.
full re condition.
5.
5.
After the time set above or if RESET, the panel reverts to step 1.
After the time set above or if RESET, the panel reverts to step 1.
Note: 220Ω ‘Evacuate’ call points should be used on such zones to provide an instant un-delayed alarm.
A 470Ω call point will be included in the dependency delay sequence.
Dependency ‘C’ will apply the following sequence:
1.
1.
The rst detector or 470Ω call point alarm will indicate at the control panel but not activate the
The rst detector or 470Ω call point alarm will indicate at the control panel but not activate the
sounders.
sounders.
2.
2.
The panel will not activate a full re condition unless a second detector or 470Ω call point is
The panel will not activate a full re condition unless a second detector or 470Ω call point is
activated in the same or any other zone.
activated in the same or any other zone.
Note: A 220Ω ‘Evacuate’ call point can be used on such zones to provide an instant un-delayed alarm.

Related product manuals