Installer parameters.... cont.
PA:10 - Return to factory settings
This parameter lets you return programs and parameters to the factory settings.
Press key 5
+ or - to choose Yes (reset) or no (no reset).
Confirm using the
OK key to pass to the next parameter.
CF9 (= cfg) - Radio links
This parameter enables the establishment of radio links between the receiver and the transmitter.
Press key 5
+ or - to select:
ON (configuration),
CH1: Establishment of radio links,
CH2: Scene mode (function not available)
PA:11 - Return to factory RF link settings
This parameter allows a reset to the factory RF link settings.
PA:12 - Software version
This parameter displays which version of the software is installed in the product.
Press
OK to exit from parameter adjustments.
Choice of the mode of regulation as a function of the heating/air-conditioning generator.
- ON/OFF regulation: suitable for all types of installation (gas boiler with or without flue, fuel oil boiler, heat
pump, heating/air-conditioning circulation).
- PID regulation: suitable for the following installations: heating or cooling circulation, gas boiler. The most
accurate regulation.
User parameters
To access the user parameters, press key 1 menu to place the cursor under and confirm using the
OK key.
Configuration
fct
cfg
fct
LED
cfg
LED
LED
fct
cfg
fct cfg
PA:1 - default duration of the temporary override
This parameter allows you to input a default, restart time delay. Possible delay times are the following:
1 hour, 2 hours, 3 hours, 4 hours, 5 hours and 12 hours. The restart delay is set to 1 hour by default.
PA:1 and flash. Press key 5 + or - to modify the restart delay.
Confirm using the
OK key to pass to the next parameter.
PA:2 - Backlighting
Backlighting is activated (
on) by default.
Press key 5
+ or - to deactivate it (oFF).
Confirm using the
OK key to pass to the next parameter.
PA:3 - Temperature calibration
This parameter lets you adjust the value displayed by the thermostat if you measure a dierent
ambient temperature to that which the thermostat measures.
Press key 5
+ or - to modify the temperature within a range of +/-3 °C.
Confirm using the
OK key.
PA:4 - 2nd Comfort temperature level
This parameter allows you to select one
or two Comfort temperature levels.
It is only applicable during programming of the free program (
P4).
Press key 5
+ or - to choose 1 or 2 .
Confirm using the
OK key to pass to the next parameter.
Parameter
PA:4 is set to 1, single Comfort level, by default.
Transmitter Receiver
Power supply : 2 alkaline batteries 1.5V (type LR03)
Battery lifespan : 2 years
Static dierential (On/O regulation) : < 0.3 °C
Power reserve : 10 min
Adjustment range
- Comfort température: +5 °C à +30 °C
- Comfort 2 temperature: +5 °C to +30 °C
- Eco temperature : +5 °C to +30 °C
Ambient temperature display range :
0 °C to +40 °C
Operating temperature : +0 °C to +45 °C
Storage temperature : -25 °C to +70 °C
Clock operating accuracy : drifts < 1sec/day
Relative humidity : 90 % at 20 °C
IP : 30
IK : 04
Ecodesign class : 4
Pollution class : 3
Action type : 2B
Software structure : class A
Dimensions (l x h x d) : 97 x 138 x 30
Transmission frequency : 868.3 MHz
Transmitter duty cycle : 1%
Receiver category 2
Maximum emission power RF : 25mW
Power supply : 230 V v +10/-15% 50Hz
Minimum load : 12 V 100 mA
Output : 1 unconnected reversing contactor
Trip values : AC1: 8 A 230 V v max
Inductive : 3 A (cos ϕ = 0.6)
Radio frequency : 868.3 MHz
Receiver category : 2
Transmitter duty cycle 1%
Protection rating : IP43
Insulation class : II
Shock resistance : IK04
Operating temperature : -10 °C to +60 °C
Storage temperature : -20 °C to +70 °C
Flexible wire cross-section : 0,5 to 1.5 mm
2
Rigid wire cross-section : 0,5 to 2.5 mm
2
Dimensions : 130 x 60 x 27 mm
Relative humidity : 90% max. at 20 °C
Typical range : > 150 m uninterrupted and 50 m
2
paving.
Maximum emission power RF : 25mW
Upstream protection : circuit breaker 10A
Software structure : class A
Maximum operating altitude : 2000m
Voltage and current declared for the needs of EMC
emissions tests : 230V v / 0.5A
Once adjustment of these 4 parameters is carried out, the thermostat switches to auto mode and registers
these modifications.
Technical characteristics
T
R
A
N
S
M
I
T
T
E
R
Select parameter
using the menu key
1
Give a long press on OK: PA:1 displays
Give a short press on OK until CF9 (cfg)
displays
off blinks
Press +, oN blinks
Give a short press on OK :
CH1 (= zone 1) displays
R
E
C
E
I
V
E
R
The receiver switches to configuration
mode.
LED C (cfg) is continuously lit red
Select the receiver to link :
Give a short press on button A (fct) of
the receiver
LED B (fct) blinks in red/green
Creation of the link:
Give a long press on button A (fct) until
LED C (cfg) starts to blink, then release
button A (fct)
LED B (fct) blinks red/green,
LED C (cfg) is continuously red :
the link is created
T
CH1 (= zone 1) oN displays on the transmitter
for several seconds
The transmitter and receiver are now paired
T
Return to automatic mode:
Give a short press on the menu key 1
Associating the transmitter and receiver
4 6LE001012C