Indoor Unit
205
Super Match
Item Model AP60KS1ERA(S)/1U60IS2EAB(S)
Function
cooling heating
Capacity kW
15 16
Sensible heat ratio
0.74
Total power input kW
4.66 4.69
Max. power input W
6500 6500
EER or COP W/W
3.22(A) 3.41(B)
Dehumidifying capacity 10
³×m³/h
5.1
Power cable
/
Power source N, V, Hz
1, 220~230, 50
Running /Max.Running current A / A
8.4/10.5 8.4/10.5
Start Current A
/
Indoor
unit
Unit model (color)
AP60KS1ERA(S)
Fan
Type × Number
CENTRIFUGALX1
Speed(H-M-L) r/min
460/430/400±40
Fan motor input power kW
0.20
Fan motor output power kW
0.09
Air-ow(H-M-L) m³/h
1750/1500/1350
Heat
exchanger
Type / Diameter mm
inner grooved pipe/φ7.0
Total area
/
Row
3
Dimension
External
L×W×H
mm×mm×mm
1850×600×350
Package
L×W×H
mm×mm×mm
1980×660×420
Drainage pipe (material , I.D./O.D.) mm
/
Controller (O-Optional,S-Standard)
Wired
YR-E17(O) OR YR-E16A(O)
Infrared
YR-HD01(S)
Fresh air hole dimension mm
/
Electricity heater kW
0
Sound power Noise level (H-M-L) dB(A)
69
Sound power Noise level (H-M-L) dB(A)
51/48/44
Weight (Net / Shipping) kg / kg
57/65
Piping
Refrigerant
Type / Charge g
R410A/3600
Recharge quantity g/m
45
Pipe
Liquid mm
9.52
Gas mm
19.05
Between
I.D &O.D
MAX.Drop m
30
MAX.Piping length m
50
Norminal condition: indoor temperature (cooling): 27
DB/19
WB, indoor temperature (heating): 20
DB
Outdoor temperature(cooling): 35
DB/24
WB, outdoor temperature(heating): 7
DB/6
WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser