EasyManua.ls Logo

Haier AB18CS1ERA - Page 225

Haier AB18CS1ERA
448 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Outdoor Unit
223
Super Match
Item Model 1U48IS1EAB(S)
Power cable H05RN-F 4G 4.0mm2
Connecting cable(including communication cable) H05RN-F 4G 2.5mm2
Power source N, V, Hz 3N~,380
400, 50Hz
Start Current A 62.5
Outdoor
unit
Unit model (color) 1U48IS1EAB(S)
WHITE
Compressor
Model / Manufacture/
place
JT160G-P8Y1/XIAN DAIKIN
CORPORATION
Oil model PVE(FV50S or the same)
Oil charging 1600CM3
Type SCROOL 1
Fan
Type × Number axial×2
Speed r/min 850±40
Fan motor input power kW 0.70×2
Fan motor output power kW 0.130×2
Air-ow(H-M-L) m³/h 6500
Heat
exchanger
Type / Diameter mm TP2M/Φ7.94
Row/Fin pitch 2 1.5
Total area 1.17
Dimension
External
L×W×H
mm×mm×mm 960×340×1250
Package
L×W×H
mm×mm×mm 1095×410×1400
Drainage pipe (material , I.D./O.D.) mm none
Refrigerant control method mm/mm electronic valve 3.0mm
Defrosting auto
Volume of Accumulator L 4.0
Noise level dB(A) 60
Type of four way valve SHF-20A-46
material of reduce noise XPE
crankcase heater power W 38
Weight(Net / Shipping) kg / kg 108/118
Piping
Refrigerant
Type / Charge g R410A/3600
Maximum pipe length
without recharge
refrigerant
m 5
Recharge quantity g/m 45
Pipe
Liquid mm 9.52
Gas mm 19.05
Connecting Method ared
Between I.D
&O.D
MAX.Drop m 30
MAX.Piping length m 50
Norminal condition: indoor temperature (cooling): 27
DB/19
WB, indoor temperature (heating): 20
DB
Outdoor temperature(cooling): 35
DB/24
WB, outdoor temperature(heating): 7
DB/6
WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound
intensity meter. It is a sound pressure noise level.

Other manuals for Haier AB18CS1ERA

Related product manuals