Item Model AB48ES1ERA(S)/1U48LS1EAB(S)
Function cooling heating
Capacity kW 13.0 14.1
Sensible heat ratio 0.8
Total power input kW 4.62 4.85
Max. power input W 6500 6500
EER or COP W/W 2.81(C) 2.91(E)
Dehumidifying capacity 10
‐
³×m³/h 4.5
Power cable /
Power source N, V, Hz 1N~,220~230, 50/60
Running /Max.Running current A / A 8.0/10.5 8.1/10.5
Start Current A 64
Indoor
unit
Unit model (color) AB48ES1ERA(S)
Fan
Type × Number CENTRIFUGALX1
Speed(H-M-L) r/min 890/760/520
Fan motor input power kW 0.15
Fan motor output power kW 0.055
Air-ow(H-M-L) m³/h 1650/1400/1300
Heat exchanger
Type / Diameter mm inner grooved pipe/φ7.0
Total area m² /
Dimension
External
(
L×W×H
)
mm×mm×mm 840/840/290
Package
(
L×W×H
)
mm×mm×mm 910/910/370
Drainage pipe (material , I.D./O.D.) mm PVC 26/32
Controller (O-Optional,S-Standard)
Wired YR-E14(O)
Infrared YR-HD(S)
Fresh air hole dimension mm 100
Electricity heater kW 0
Noise level (H-M-L) dB(A) 49/47/44
Weight (Net / Shipping) kg / kg 31/37
Panel
Model PB-950JB
External dimensions(W/D/H) mm 950/950/60
Shipping dimensions(W/D/H) mm 985/985/115
Net weight/Shipping weight kg 6/7.5
Piping
Refrigerant
Type / Charge g R410A/2600
Recharge quantity g/m 45
Pipe
Liquid mm 9.52
Gas mm 19.05
Between I.D &O.D
MAX.Drop m 30
MAX.Piping length m 50
Norminal condition: indoor temperature (cooling): 27
℃
DB/19
℃
WB, indoor temperature (heating): 20
℃
DB
Outdoor temperature(cooling): 35
℃
DB/24
℃
WB, outdoor temperature(heating): 7
℃
DB/6
℃
WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter. It is
a sound pressure noise level.