378
Super Match
1U48LS1EAB(S) 1U48IS1EAB(S) 1U60IS1EAB(S) 1U60IS2EAB(S)
Flash times
of LED1
Trouble description Analyze and diagnose Remark
1 EEPROM faulty Wrong EEPROM used Non-resumable
3
Compressor overcurrent/
phase sequence wrong
Overcurrent after compressor running or power supply phase
sequence wrong before compressor running.If ir occurs 3 timesin
1 hour,conm the failure, the former twice will not alarm.
Non-resumable
6
High/Low voltage
protection
Phase voltage too high or too low(over 270V last 2 seconds;
below 187V last 2 senconds).If it occurs 3 times in 30 minutes,
conrm the falure.
Non-resumable
8
Proctection of
diacharging temp. too
high
After compressor starts up, if TD is over 120degree, 10 seconds
later compressor stops, if it occurs 3 times in 1 hour, conrm the
failure.
Non-resumable
9 DC fan motor faulty
If it occurs times in 1 hour, conrm the failure, the former twice
will not alarm
Non-resumable
10
Defrost temp. sensor
abnormal
Sensor is dectected below 20 or over 1000 for 60 seconds;
temperature detected too high(0ver 68degree last 3 senconds or
over 63degree last 20 senconds)
Resumable
11
Suction temp.sensor
abnormal
Sensor is detected below 20 or over 1000 for 60s, but in
defrosting or within 6min after defrosting, it will not alarm.
Resumable
12
Ambient temp. sensor
abnormal
Sensor is detected below 20 or over 1000 for 60s, but in
defrosting or within 6min after defrosting, it will not alarm.
Resumable
13
Discharging temp. sensor
abnormal
After compressor running for 3min, sensor is detected below 20
or over 1000 for 60s.
Resumable
15
Comminication between
indoor and outdoor
abnormal
Indoor unit cannot be inspected for 4min continuously. Resumable
16
Lack of refrigerant or
diacharging pipe blocked
If it occurs 3 times in 1 hour, conrm the failure Non-resumable
17
4-way valve converse
abnormal
If it occurs 3 times in 1 hours, conrm the failure. Non-resumable
25
Compressor low current/
current imbalance
between two phase
Low current after compressor running or current imbalance
between two phase after compressor running. If it occurs 3 times
in 1 hour, conrm the failure, the former twice will not alarm.
Non-resumable
42
High pressure switch
abnormal
After compressor running for 3min, if switch is detected
unconnected for 30s, it alarms.If it occurs 3 times in 1 hours,
conrm this failure, or if TCM is over 68degree for 10s for 3 times.
Non-resumable
43
Low pressure switch
abnormal
After compressor running for 3min, if switch is detected
unconnected for 30s, it alarms.If it occurs 3 times in 1 hour,
conrm this failure. If it occurs 3 times in 1 hour,conrm the
failure,but in defrosting or within 6min after defrosting, it will not
alarm.
Non-resumable
Note:
1.The ash times of outdoor mainboard(ECU) LED1(red color) indicates the malfuction code. for example, LED1 ash 3times
, the malfuction code is 3.
2.The ash times or malfuction code of indoor unit can also indicates the malfuction code too,the method to conrm please
refer to the indoor unit manul.
150510198