Super Match
Unit number setting
(This function is intended for debugging by technical personnel. The wired controller No. with no permission of
address setting by indoor DIP switch setting displays grey, with access to checking and no access to changing the
communication No.)
Figure 18 Figure 19
1. Proceed through main interface→Menu→Other →enter the password of the technical personnel→press "Enter"
key→Addressing→press "Enter" to enter the interface as shown in Figure 18.
2. Wired controller number, as shown in Figure 18, is set by DIP switch of indoor unit. If one wired controller
controls one unit, there is only 01; it displays the unit numbers corresponding to the indoor units in operation.
3. When in the interface as shown in Figure 18, if there are more than one wired controller numbers, use the
"upward", "downward", "leftward" and "rightward" keys to select a unit number and press "Enter" key; Then the POP
window as shown in Figure 19 will appear.
4. When the window in Figure 19 has popped out, the communication unit number of this controller can be
set (communication addresses between the outdoor unit and indoor unit) 1-64; use the leftward and rightward
keys to adjust the unit digits and tens digits and use the upward and downward keys to adjust the values on the
corresponding digits; then press "Enter" or "Cancel" to return to the interface as shown in Figure 18.
5. The controller address equals the corresponding value of indoor unit's group address dial code plus 1.