Pay special care to the following and check after installation
Item to the checked Improper installation may cause
Is indoor unit rmly installed? Unit might fall down, make vibration or noise.
Is gas leakage check performed? This may lead to gas shortage.
Is unit properly insulated? Dew or water drop may occur.
Is water drainage smooth? Dew or water drop may occur.
Is power voltage meet that stipulated on the nameplate? Problem may occur or parts got burned.
Is wiring and piping correctly arranged? Problem may occur or parts got burned.
Is unit safely grounded? There might be a danger of electric shock.
Is wire size correct? Problem may occur or parts got burned.
Are there any obstacles on air inlet and outlet grill of
indoor and outdoor unit?
This may cause poor cooling.
Is record made for piping length and refrigerant
charging amount?
It is hard to control refrigerant charging amount.
Attention: after nishing installation,conrm no refrigerant leakage.