64
Super Match
Item Model AC48FS1ERA(S)/1U48LS1ERA(S)
Function cooling heating
Capacity kW 12.5(6.0-14.5) 14.1(6.0~16.5)
Sensible heat ratio 0.74
Total power input kW 3.89
(
2.0---6.0) 4.10
(
2.0---6.0)
Max. power input W 5600 5600
EER or COP W/W 3.21(A) 3.44(B)
Dehumidifying capacity 10
‐
³×m³/h 5.0
Power cable /
Power source N, V, Hz 1PH, 220-230V~, 50/60Hz
Running /Max.Running current A / A 18.5(2.7-26)/26 19.2(2.7-26)/26
Start Current A /
Indoor
unit
Unit model (color) AC48FS1ERA(S)
Fan
Type × Number CENTRIFUGALX4
Speed(H-M-L) r/min (1250/1150/1100)r/min
Fan motor input power kW 0.18
Fan motor output power kW 0.105
Air-ow(H-M-L) m³/h 2000/1800/1400
Heat exchanger
Type / Diameter mm inner grooved pipe/φ7.0
Total area m² 0.312
Dimension
External
(
L×W×H
)
mm×mm×mm 1580/700/240
Package
(
L×W×H
)
mm×mm×mm 1710/790/315
Drainage pipe (material , I.D./O.D.) mm PP 20/25
Controller (O-Optional,S-Standard)
Wired YR-E17(O) YR-E16A(O)
Infrared YR-HD(S)
Fresh air hole dimension mm 200
Electricity heater kW 0
Sound power Noise level (H-M-L) dB(A) 66
Sound pressure Noise level (H-M-L) dB(A) 53/51/49
Weight (Net / Shipping) kg / kg 54/61
Piping
Refrigerant
Type / Charge g R410A/2850
Recharge quantity g/m 45
Max. pipe length without charge
refriigerant
m 20
Pipe
Liquid mm 9.52
Gas mm 19.05
Between I.D &O.D
MAX.Drop m 30
MAX.Piping length m 50
Norminal condition: indoor temperature (cooling): 27
℃
DB/19
℃
WB, indoor temperature (heating): 20
℃
DB
Outdoor temperature(cooling): 35
℃
DB/24
℃
WB, outdoor temperature(heating): 7
℃
DB/6
℃
WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter. It is a