66
Super Match
Item Model AC60FS1ERA(S)/1U60IS1EAB(S)
Function cooling heating
Capacity kW 15.5 16.8
Sensible heat ratio 0.74
Total power input kW 5.13 5.23
Max. power input W 6500 6500
EER or COP W/W 3.02
(
B
)
3.21
(
C
)
Dehumidifying capacity 10
‐
³×m³/h 5.6
Power cable /
Power source N, V, Hz 1, 220~230, 50/60
Running /Max.Running current A / A 8.6/10.5 8.8/10.5
Start Current A /
Indoor
unit
Unit model (color) AC60FS1ERA(S)
Fan
Type × Number CENTRIFUGALX4
Speed(H-M-L) r/min (1250/1150/1100)r/min
Fan motor input power kW 0.18
Fan motor output power kW 0.105
Air-ow(H-M-L) m³/h 2000/1800/1400
Heat exchanger
Type / Diameter mm inner grooved pipe/φ7.0
Area 3
Total area m² 0.312
Dimension
External
(
L×W×H
)
mm×mm×mm 1580/700/240
Package
(
L×W×H
)
mm×mm×mm 1710/790/315
Drainage pipe (material , I.D./O.D.) mm PP 20/25
Controller (O-Optional,S-Standard)
Wired YR-E14(O)
Infrared YR-HD(S)
Fresh air hole dimension mm 200
Electricity heater kW 0
Noise level (H-M-L) dB(A) 53/51/49
Weight (Net / Shipping) kg / kg 54/61
Piping
Refrigerant
Type / Charge g R410A/3300
Recharge quantity g/m 45
Pipe
Liquid mm 9.52
Gas mm 19.05
Between I.D &O.D
MAX.Drop m 30
MAX.Piping length m 50
Norminal condition: indoor temperature (cooling): 27
℃
DB/19
℃
WB, indoor temperature (heating): 20
℃
DB
Outdoor temperature(cooling): 35
℃
DB/24
℃
WB, outdoor temperature(heating): 7
℃
DB/6
℃
WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter. It is a
sound pressure noise level.