107
WARNING
1) Do not use mineral oil on ared part.
2) Prevent mineral oil from getting into the system as this would educe the lifetime of the units.
3) Never use piping which has been used for previous installations. Only use parts which are delivered with the
unit.
4) Do never install a drier to this R32 unit in order to guarantee its lifetime. The drying material may dissolve and
damage the system.
5) Incompete aring may cause refrigerant gas leakage.
In order to protect the environment, be sure to pump down when
relocating or disposing of the unit.
1) Remove the valve caps from liquid stop valve and gas stop valve.
2) Carry out forced cooling operation.
3) After ve to ten minutes, close the liquid stop valve with a hexagonal
wrench.
4) After two to three minutes, close the gas stop vaile and stop forced
cooling operation.
9.1 Electric wiring
The air conditioner must use special circuit, and wiring by the qualied electrician according to the wiring rules
specied in national standard.
The grounding wire and the neutral wire shall be strictly separated. Connect the neutral wire with grounding wire is
incorrect. The explosion-proof electric leakage breaker must be installed.
All the electric wire must be copper wire.Power supply: 1PH, 220-240V-, 50/60Hz.
The wiring method of power line is Y connection. If the power line is damaged, in order to avoid risk of electric
shock, it must be replaced
by the manufacturer or its repair center or other similar qualied person.The connecting cable must be shielded.
Fuse: T3.15A 250VAC(Electronic control unit) T25A 250VAC(Power circuit board).
Please check the circuit diagram about the fuse replaced, explosion-proof fuse.
The specication of power cable is H05RN-F3G 4.0mm
2
.
The specication of cable between indoor unit to outdoor unit is H05RN-F4G 2.5mm2.
9.2 Wiring method
• Wiring method of orbicular terminals
For the connection wire with orbicular terminals, its wiring method is
as shown in the right gure: remove the connecting screw, put the
screw through the ring on the end of the wire, then connect to the
terminal block and fasten screw.
• Wiring method of straight terminals.
For the connection wire without orbicular terminals, its wiring method
is: loosen the connection screw, and insert the end of the connection
wire completely into the Terminal block, then fasten the screw.
Slightly pull the wire outwards to conrm it is rmly held.
8. Pump down operation
9. Wiring work