3)BM3 instruction
2)BM2 instruction
BM2-1
Quiet running
function
0 System functions normally without quiet function
1 Quiet running functions
BM2-2 Anti-snow function
0 System functions normally without anti-snow function
1 Anti-snow functions
BM2-3 No definition 0 Default is 0. 1 is forbidden
BM2-4 No definition 0 Default is 0. 1 is forbidden
BM2-5
BM2-6
Outdoor installation
condition selection
BM2-5 BM2-6 Outdoor installation condition selection
0 0 Default setting (Normal installation condition )
0 1 Low humidification in winter condition
1 0 High humidification in winter condition
1 1 Default setting (Normal installation condition )
BM2-7
BM2-8
Piping length
selection
BM2-7 BM2-8 Piping length selection
0 0 Default setting (Medium piping length)
0 1 Long piping length
1 0 Short piping length
1 1 Default setting (Medium piping length)
BM3-1
BM3-2
BM3-3
Outdoor model setting
BM3-1 BM3-2 BM3-3 Outdoor model
0 0 0
Three pipes model
(applied to 084A PCB)
Single class
0 0 1
MX6-S model
(applied to 084C PCB)
0 1 0
Water Cooled VRF model
(applied to 084C PCB)
0 1 1 Reserved
1 0 0 Reserved
1 0 1 Reserved
1 1 0 Reserved
1 1 1 Reserved
BM3-4
3Ph, 50Hz/60Hz
selection
0 50Hz
Single class
1 60Hz
BM3-5
BM3-6
BM3-7
BM3-8
Outdoor HP setting
BM3-5 BM3-6 BM3-7 BM3-8 Outdoor HP
0 0 0 0 6HP
0 0 0 1 8HP
0 0 1 0 10HP
0 0 1 1 12HP
0 1 0 0 14HP
0 1 0 1 16HP
0 1 1 0 18HP
0 1 1 1 20HP
1 0 0 0 22HP
1 0 0 1 24HP
1 0 1 0 26HP
1 0 1 1 28HP
Other’s reserved
Note:
Oil temperature too low protection
See BM1-3 (BM1 introduction table).