EasyManua.ls Logo

Haier AD482MPERA - Page 239

Haier AD482MPERA
297 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
238
4)BM4 instruction
5)BM5 instruction
BM5_1
~
BM5_4
Outdoor motor selection
BM5_1 BM5_2 BM5_3 BM5_4 Selection item
1 1 0 0 Dual fan motor(375W)
0 0 1 1 Single fan motor(750W)
BM5_5
~
BM5_8
Inverter board selection
BM5_5 BM5_6 BM5_7 BM5_8 Selection item
0 0 1 1 180° inverter board
Monitor tooIs
Monitor code is as following:
Press button: SW2(UP), SW1(DOWN) are the button switch
Rotary switch: SW9, SW10, SW11 are setable from 0 to 15.
( Note: on code wheel with letters, A for 10, B for 11, C for 12, D for 13, E for 14, F for 15)
Display part: LED1, LED2, LED3, LED4, 4 digital tubes are ranked from left to right.
Display content is as follow:
BM4-1
Drop selection among
indoors
0 Without drop among indoors
Group class (valid for
physical host)
1 With drop among indoors
BM4-2
Fan motor operation setting
of stopped slave units when
the master unit is heating
0 Stopped
Single class
1 Operating
BM4-3
Outdoor static pressure
selection
0
Max. rotating speed of outdoor fan motor is 14 (factory
default)
Single class
1
Max. rotating speed of outdoor fan motor is 15 (82Pa static
pressure)
BM4-4
BM4-5
Outdoor mode setting (not
suitable for 3 pipes model)
BM4-4 BM4-5 Mode setting
Group class (valid for
physical host)
0 0 Normal
0 1 Cooling only
1 0 Heating only
1 1 VIP
BM4-6
BM4-7
BM4-8
Indoor units priority setting
(Not suitable for 3 pipes
model. Available when the
outdoors are set in normal
or VIP mode)
BM4-6 BM4-7 BM4-8 Priority setting
Group class (valid for
physical host)
0 0 0 First priority
0 0 1 Last priority
0 1 0 Cooling priority
0 1 1 Heating priority
1 0 0 Majority priority
1 0 1 Reserved (first priority)
1 1 0 Reserved (first priority)
1 1 1 Reserved (first priority)

Other manuals for Haier AD482MPERA