EasyManua.ls Logo

Haier AP48KN1EAA - Page 37

Haier AP48KN1EAA
54 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Single Split
35
Type 1: Standard defrost
(1) If Tr≥-2
, when Tp≤-6
, enter defrost.
(2) If -12
Tr
-2
, when Tp≤-6
, please refer to the following chart.
(3) No matter the ambient temperature, when Tp≤-16
, enter defrost.
Type 2: Non-standard defrost (rectify defrost data by the device)
(1) If Tr≥6
, when Tp≤-6
, enter defrost.
(2) If -18
Tr
-6
, when Tp≤-6
, please refer to the following chart.
(3) No matter the ambient temperature, when Tp≤-18
, enter defrost.