Single Split
39
10. Failure code
WCR : Failure code in
pannel
CCR : Run lamp flash times
SN
WCR
CCR Failure description
1
E0
10
Float switch is disconnected 25min or longer.
2
E1
1
Indoor ambient s
ensor is open
-
circuit or short
-
circuit for
2min or longer.
3
E2
2
Indoor pipe s
ensor is open
-
circuit or short
-
circuit for 2min or
longer.
4
E3
3
Outd
oor ambient s
ensor is open
-
circuit or short
-
circuit for
2min or longer.
5
E4
4
Outdoor discharge/pipe temp. s
ensor is open
-
circuit or short
-
circuit for 2min or longer.
6
E5
5
Current is too high or the turn of 3 phase is wrong.
7
E6
6
High or low pressure swi
tch is open circle for 2 minutes.
8
E8
8
Communication problem between indoor and controller.
9
E9
9
Communication problem between indoor and outdoor unit.
0150514714