– 16 –
  Constant Fan
In Constant Fan mode, the Zoneline operates in 
High Fan mode regardless of fan setting.  
This feature allows the fan to operate even when 
the Zoneline is set in the OFF position.  This 
will allow continuous air circulation in the room 
even if the Zoneline is turned off.  This function is 
available as a selectable option through the use 
of an Auxiliary Set button mode.  The selection of 
this function will override the CDC provision.
Fan Operation
Both fan motors are variable speed DC fan 
motors with RPM feedback and regulation control.  
Any time a fan is energized, the control checks 
that the fan reaches the target RPM speed +/- 
150 RPMs.  If the target cannot be met, the fan 
motor will shut down for 15 minutes, and will 
set a fault code.  It will reattempt to run every 
15 minutes.  If the fan motor reaches the proper 
RPM, the fault code will clear.  If the fault does 
not clear, the fault code will be stored in memory 
and the Zoneline will function as follows:
•  For detected indoor fan failures, the Zoneline 
will cease all operation until the next try to 
energize the fan.
•  For detected outdoor fan failures, the 
Zoneline will revert to Stage 3 heating if it is 
trying to run in Stage 1 or Stage 2 heating.  
The Zoneline will then run the indoor fan only 
if it is trying to run in Cooling Mode.