Electric wiring and the application
Indoor power source and communication wiring
Item
Indoor
total
current (A)
Power
cable
section
(mm
2
)
Wire
length
(m)
Rated
current of
overcurrent
breaker
(A)
Rated current of residual
circuit breaker(A)
Ground fault
interruptor(mA)
response time(S)
Communication wire
section
Outdoor/
indoor
(mm
2
)
Indoor/
indoor
(mm
2
)
<10 2 20 20 20A, 30mA, below 0.1s
2-core × (0.75-2.0mm
2
)
shielded wire
≥10 and <15 3.5 25 30 30A, 30mA, below 0.1s
≥15 and <22 5.5 30 40 40A, 30mA, below 0.1s
≥22 and <27 10 40 50 50A, 30mA, below 0.1s
Power cable and communication wire must be xed rmly.
Each indoor must be grounded well.
When power cable exceeds the range, increase the gauge appropriately.
Shielded layer of communication wires must be connected together and be earthed at single
point.
Communication wire total length cannot exceed 1000m.
Communication wire for wired controller
The shielding lay of the signal line must be grounded at one end.
The total length of the signal line shall not be more than 250m.
Length of Signal Line (m) Wiring Dimensions
≤250 0.75mm
2
× 3 core shielding line