Circuit diagrams
 
Domestic air conditioner
11.4.12 High work-intense protection 
Electrify the machine again and turn it on with the 
remote controller, check whether the wind 
temperature is below 65ć
The malfunction is reported 
after the machine has run 
for some time? 
1 ǃ Check room temperature and 
pipe temperature sensor. 
2ǃthe temperature monitoring circuit 
of the indoor mainboard   
The indoor unit blows poorly 
due to blocked filters or poor 
condition of the fan? 
1) Clean the filters
2) Reinstall the fan.
Use some tools to measure the pressure of systemˈ
YES 
NO
YES 
NO
Method of 
malfunction detection 
Malfunction detection 
conditions
Troubleshootin
High work-intense control is activated in the heating mode if the temperature being 
sensed b
 the heat exchan
er thermistor exceeds the limit.
Activated when the temperature being sensed by the heat exchanger rises above 
65ć twice in 30 minutes.
ŶFaulty electronic expansion valve 
ŶDirty heat exchanger 
ŶFaulty heat-exchange sensor 
ŶInsufficient gas 
Supposed causes 
* Caution
Be sure to turn off power switch before connect or disconnect connector,      or else 
parts damage may be occurred. 
LED1  flash 21 times
Outdoor diplay