en.haiwell.com Haiwell PLC -- Load Cell Module User Manual
4. Environmental Specification
Environment Specification
Operating temperature:0~+55℃ Storage temperature:-25~+70℃ Humidity: 5~95%RH, No condensation
10~57 HZ, amplitude=0.075mm, 57HZ~150HZ acceleration=1G, 10 times each for X-axis, Y-axis and Z-axis
15G, duration=11ms, 6 times each for X-axis, Y-axis and Z-axis
DC EFT:±2500V Surge:±1000V
Avoid dust, moisture, corrosion, electric shock and external shocks
5. Module Parameter Table
7.5/15/30/60/120/240/480/960Hz
Static weighing≤ 0.02% FS
5VDC ±5% , 125mA ( it can connect with 4 load Cells each 350 Ω )
4- line connection or 6-line connection load Cells
Maximum distance to
connect the sensor
6. Load Cell Connections
Wiring Diagram (First generation load cell module)
4-wire sensor and instrument connection 6-wire sensor and instrument connection
Wiring Diagram (Second generation load cell module)
SIG+
EXC+
SIG-
EXC-
EXC+
EXC-
SIG+
SIG-