Multi Loop Controller
30
Register address (HEX) Parameter
Description
Property
(R/W)
Setting range Unit
Initial
value
CH1 CH2 CH3 CH4
n : Number
of channel
107
(6B)
207
(CF)
307
(133)
407
(197)
RJC
Reference
junction
compensation
temperature
value
R EU (0 ~ 100%) -
108
(6C)
208
(D0)
308
(134)
408
(198)
TC
Thermo couple
(TC) value
R EU (0 ~ 100%) -
109
(6D)
209
(D1)
309
(135)
40
(199)
INP Set input type R/W
0~18: thermo couple (TC)
20~23: Resistance Temperature Detector (RTD)
30~ 32:direct current voltage (DCV)
* Refer to input type
ABS
1
(TC
K Type)
110
(6E)
210
(D2)
310
(136)
410
(19A)
CHMD Set channel mode R/W
0: Stop mode
1: Monitor mode
2: Run mode
ABS
0
(stop
mode)
111
(6F)
211
(D3)
311
(137)
411
(19B)
AT
Run PID auto
tuning(AT)
R/W
0: PID auto tuning (AT) stop
1: PID auto tuning (AT) start
ABS 0
112
(70)
212
(D4)
312
(138)
412
(19C)
OUT Input type R
0:RELAY
1:SSR
2.SCR
ABS
Follow
product
specs
113(71)
~
120(78)
213(D5)
~
220(78)
313(139)
~
320(78)
413(19D)
~
420(78)
EV.1DLY
~
EV.8DLY
Set event delay R/W 0 ~ 9999 Sec. 0
121
(79)
221
(DD)
321
(141)
421
(1A5)
EV.1TY
Set event channel 1
type
R/W
None(OFF)
1:Deviation high limit
2: Deviation low limit
3. Deviation high/low limit
4: Within deviation scope
5: Deviation high limit (stand by)
6: Deviation low limit (stand by)
7. Deviation low/high limit
(stand by)
8. Within deviation (stand by
9:PV high limit
10: PV low limit
11: PV high limit (stand by)
12:PV low limit (stand by)
13: SV high limit
14: SV low limit
15: Loop break (LBA)
16: -
17: Run start (RUN)
18: Run/monitor mode
(READY)
19: FAIL
ABS 0 (OFF)
122(7A) 222(DE) 322(142) 422(1A6) EV.1VL
Event set value of
event channel 1
R/W EUS (0 ~ 100%)
EUS
(0%)
123(7B) 223(DF) 323(143) 423(1A7) EV.1HY
Event channel 1,
event hysteresis
R/W EUS (0 ~ 10%)
EUS
(0.2%)
124(7C)
~
144(90)
224(E0)
~
244(F4)
324(144)
~
344(158)
424(1A8)
~
444(1BC)
EV.2~
~
EV.8~
Set event channel
2~8 event type, set
value and hysteresis
R/W Same as event channel 1
145
(91)
245
(F5)
345
(159)
445
(1BD)
LBA
Set loop break
event time
R/W 0(OFF), 1~7200 Sec. 0 (OFF)
146
(92)
246
(F6)
346
(15A)
446
(1BE)
LBD
Set loop break
event dead band
R/W EUS (0 ~ 100%)
EUS
(100%)
147
(93)
247
(F7)
347
(15B)
447
(1BF)
EVSTOP
Set stop running at
event occurrence
R/W
0: continuous run
1: stop run
ABS
0
(continuous
run)
151
(97)
251
(FB)
351
(15F)
451(1C3)
PB
Set proportional
band
R/W EUS (0 ~ 100%)
EUS
(2%)
152(98) 252(FC) 352(160)
452(1C4)
TI Set integral time R/W 1 ~ 3600 Sec. 240
153(99) 253(FD) 353(161)
453(1C5)
TD
Set differentiation
time
R/W 1 ~ 3600 Sec. 60
154(9A) 254(FE) 354(162)
454(1C6)
AP
Set 2 DOF PID
ALPHA
R/W 1 ~ 100 ABS 50
155(9B) 255(FF)
355(163)
455(1C7)
MR Set Manual Reset R/W 0.0 ~ 100.0 % 0.0