EasyManua.ls Logo

HANYOUNG NUX ML-D2H - Page 33

HANYOUNG NUX ML-D2H
54 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
31
Before staring Installation Operation Specifications
Register address (HEX) Parameter
Description
Property
(R/W)
Setting range Unit Initial value
CH1 CH2 CH3 CH4
n : Number of
channel
154(9A) 254(FE) 354(162)
454(1C6)
AP Set 2 DOF PID ALPHA R/W 1 ~ 100 ABS 50
155(9B) 255(FF) 355(163)
455(1C7)
MR Set Manual Reset R/W 0.0 ~ 100.0 % 0.0
156(9C)
256(100) 356(164) 456(1C8)
CT Set control cycle R/W 1 ~ 100 Sec.
RELAY
: 30 Sec.
S.S.R :
2초 Sec.
157(9D)
257(101)
357(165)
457(1C9)
PO
Set emergency output
R/W 0.0 ~ 100.0
% 0
158(9E) 258(102) 358(166)
458(1CA)
HYS
Set hysteresis at ON/OFF
control
R/W EUS (0 ~ 10%)
EUS
(0.2%)
159(9F) 259(103) 359(167)
459(1CB)
RO
Set output at stop,
monitor status
R/W 0.0 ~ 100.0 % 0
160(A0)
260(104) 360(168)
460(1CC)
RUP
Set SV increase
temperature at RAMP
control
R/W EUS (0 ~ 100%)
EUS (0%)
161(A1) 261(105)
361(169)
461(1CD)
RDN
Set SV decrease
temperature at RAMP
control
R/W
EUS (0 ~ 100%)
EUS (0%)
162(A2) 262(106)
362(16A)
462(1CE)
RMIN
Set SV change time (min.)
at RAMP control
R/W 0 ~ 1000 Minute 0
163(A3) 263(107)
363(16B) 463(1CF)
RHRS
Set SV change time (hr.)
at RAMP control
R/W 0 ~ 100 Hour 0
164(A4)
264(108)
364(172)
464(1D0)
DR
Set control run
R/W
0: Reverse run
(heating) control
1: Forward run (cooling)
control
ABS
0
(Reverse
run (heating)
control)
165(A5)
265(109)
365(173)
465(1D1)
OHL
Set high limit to
Manipulated Value
R/W 0.0 ~ 100.0 % 100.0
166(A6)
266(10A)
366(174)
466(1D2)
OLL
Set low limit to
Manipulated Value
R/W
0.0 ~ 100.0 % 0.0
171(AB) 271(10F) 371(173) 471(1D7) BS Set input correction R/W EUS (-100 ~ 100%) EUS (0%)
172(AC) 272(110) 372(174) 472(1D8) FL Set input filter R/W 0 ~ 100 ABS 0
173(AD) 273(111) 373(175) 473(1D9) SVH Set SV high limit R/W EU (0 ~ 100%) EU (100%)
174(AE) 274(112) 374(176) 474(1DA) SVL Set SV low limit R/W EU (0 ~ 100%) EU (0%)
175(AF) 275(113) 375(177) 475(1DB) FRH Set PV high limit R/W EU (0 ~ 100%) EU (100%)
176(B0) 276(114) 376(178) 476(1DC) FRL Set PV low limit R/W EU (0 ~ 100%) EU (0%)
177(B1) 277(115) 377(179) 477(1DD) SLH
Set scale high limit at
DCV input setting
R/W EU (0 ~ 100%) mV EU (100%)
178(B2) 278(116) 378(17A) 478(1DE) SLL
Set scale low limit at
DCV input setting
R/W EU (0 ~ 100%) mV EU (0%)
179(B3) 279(117) 379(17B) 479(1DF) DOT Set decimal point R/W
0 ~ 3 :
decimal point digit
ABS 0