31
Before staring Installation Operation Specifications
Register address (HEX) Parameter
Description
Property
(R/W)
Setting range Unit Initial value
CH1 CH2 CH3 CH4
n : Number of
channel
154(9A) 254(FE) 354(162)
454(1C6)
AP Set 2 DOF PID ALPHA R/W 1 ~ 100 ABS 50
155(9B) 255(FF) 355(163)
455(1C7)
MR Set Manual Reset R/W 0.0 ~ 100.0 % 0.0
156(9C)
256(100) 356(164) 456(1C8)
CT Set control cycle R/W 1 ~ 100 Sec.
RELAY
: 30 Sec.
S.S.R :
2초 Sec.
157(9D)
257(101)
357(165)
457(1C9)
PO
Set emergency output
R/W 0.0 ~ 100.0
% 0
158(9E) 258(102) 358(166)
458(1CA)
HYS
Set hysteresis at ON/OFF
control
R/W EUS (0 ~ 10%) ℃
EUS
(0.2%)
159(9F) 259(103) 359(167)
459(1CB)
RO
Set output at stop,
monitor status
R/W 0.0 ~ 100.0 % 0
160(A0)
260(104) 360(168)
460(1CC)
RUP
Set SV increase
temperature at RAMP
control
R/W EUS (0 ~ 100%)
℃
EUS (0%)
161(A1) 261(105)
361(169)
461(1CD)
RDN
Set SV decrease
temperature at RAMP
control
R/W
EUS (0 ~ 100%)
℃ EUS (0%)
162(A2) 262(106)
362(16A)
462(1CE)
RMIN
Set SV change time (min.)
at RAMP control
R/W 0 ~ 1000 Minute 0
163(A3) 263(107)
363(16B) 463(1CF)
RHRS
Set SV change time (hr.)
at RAMP control
R/W 0 ~ 100 Hour 0
164(A4)
264(108)
364(172)
464(1D0)
DR
Set control run
R/W
0: Reverse run
(heating) control
1: Forward run (cooling)
control
ABS
0
(Reverse
run (heating)
control)
165(A5)
265(109)
365(173)
465(1D1)
OHL
Set high limit to
Manipulated Value
R/W 0.0 ~ 100.0 % 100.0
166(A6)
266(10A)
366(174)
466(1D2)
OLL
Set low limit to
Manipulated Value
R/W
0.0 ~ 100.0 % 0.0
171(AB) 271(10F) 371(173) 471(1D7) BS Set input correction R/W EUS (-100 ~ 100%) ℃ EUS (0%)
172(AC) 272(110) 372(174) 472(1D8) FL Set input filter R/W 0 ~ 100 ABS 0
173(AD) 273(111) 373(175) 473(1D9) SVH Set SV high limit R/W EU (0 ~ 100%) ℃ EU (100%)
174(AE) 274(112) 374(176) 474(1DA) SVL Set SV low limit R/W EU (0 ~ 100%) ℃ EU (0%)
175(AF) 275(113) 375(177) 475(1DB) FRH Set PV high limit R/W EU (0 ~ 100%) ℃ EU (100%)
176(B0) 276(114) 376(178) 476(1DC) FRL Set PV low limit R/W EU (0 ~ 100%) ℃ EU (0%)
177(B1) 277(115) 377(179) 477(1DD) SLH
Set scale high limit at
DCV input setting
R/W EU (0 ~ 100%) mV EU (100%)
178(B2) 278(116) 378(17A) 478(1DE) SLL
Set scale low limit at
DCV input setting
R/W EU (0 ~ 100%) mV EU (0%)
179(B3) 279(117) 379(17B) 479(1DF) DOT Set decimal point R/W
0 ~ 3 :
decimal point digit
ABS 0