EasyManua.ls Logo

Harman P43 - General Operating Information

Harman P43
26 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Harman® • P-Series Installation Manual_R3 • 2014 -___ • 09/1411 3-90-436168i
4
Termination Location and Vent Information
A. Vent Termination Minimum Clearances
Figure 4.1
Figure 4.2
#1 Preferred method (Figure 4.1)
Thismethodprovidesexcellentventingfornormaloperation
andallowsthestovetobeinstalledclosesttothewall.Two
inches from the wall is safe; however, four inches allows
betteraccesstoremovetherearpanel.Theverticalportionof
theventshouldbethreetovefeethigh.Thisverticalsection
willhelpprovidenaturaldraftintheeventofapowerfailure.
Sealpipejointswithsiliconeoraluminumtapeinadditionto
thesealingsystemusedbythemanufacturer.
Note: Do not place joints within wall pass-through.
#2 Preferred method
(Figure 4.2)
This method also provides excellent venting for normal
operationbutrequiresthestovetobeinstalledfartherfrom
thewall.Theverticalportionoftheventshouldbethreeto
vefeethighandatleast1”fromacombustiblewall.This
vertical section will provide natural draft in the event of a
powerfailure.
Sealpipejointswithsiliconeoraluminumtapeinadditionto
thesealingsystemusedbythemanufacturer.
If the stove is installed below grade be sure the vent
termination is at least 12" above grade (with outside air
only).Theoutletmustalsobe1footfromthehouse/building.
Note: Do not place joints within wall pass-through.
CAUTION
!
Keep combustible materials (such as grass, leaves,
etc.) at least 3 feet away from the ue outlet on the
outside of the building.
3 Ft.
to
Combustibles
3 Ft.
to Combustibles
3 Ft.
to
Combustibles
3 Ft.
to Combustibles

Other manuals for Harman P43

Related product manuals