EasyManua.ls Logo

Harsen GU320a - User Manual

Harsen GU320a
23 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
GU320a Controller Manual
1
CONTENT
1. Introduction…………………………………………………………………….…….2
2. Shape and connection …………………….………………………………………..2
3. Operation panel……………………………………………………………………...5
4. Installation ……..…………………………………………………………….……6
5. Control and operation……………………………….…………………………..7
6. Measuring ………………………………………………………..………………..9
7. Fault signal………………………………………………………….……………..10
8. Parameters configuration…….…………………………………………….…….11
9. LCD and menu system………………………………………………………....13
10. Communication ………………………………………………………..……….……15
11. Preparations ………………………………………………….……………….
..20
12. Troubleshooting…………………………………………………………………..21

Questions and Answers

  • C
    Christopher DominguezAug 15, 2025
    What to do if Harsen GU320a Controller “Genset” does not startup?
    • S
      Stephanie ScottAug 15, 2025
      If the “Genset” does not startup, try the following: 1. Check the fault indicator light using the “L.TEST” key, or consult the LCD display for any fault messages. 2. Check the DC voltage of connecting terminal “B10” of the controller. If there's no voltage, inspect the fuse. If the voltage is low, charge the battery. 3. Check the DC voltage of connecting terminal “B12” of the controller. If there's no voltage, the controller may be faulty and needs replacement. 4. To start the magnetic flux on the motor, connect the magnetic flux junction with the battery cathode by DC voltage meter. If the magnetic flux has voltage, it is faulty and needs replacement. If not, check the connecting line of control hold for flexibility or short circuits.
  • T
    thomasjacksonAug 18, 2025
    What to do if the Harsen Controller indicates a Diesel Starting Fault?
    • C
      Charles LeAug 18, 2025
      If the Harsen Controller indicates a Diesel Starting Fault, try these steps: 1. Check the oil fuel level. 2. Check the DC voltage of connecting terminal “B11” of the controller. If there is no voltage, the controller may be faulty and needs to be replaced. 3. Check the fuel control magnetic flux connecting line and voltage on the magnetic flux. 4. Check the fuse on one side of the alternator. 5. Check the oil fuel pipe and oil filter for any blockages. 6. If white smoke is emitting from the exhaust system, fuel is entering the generator but the diesel is not starting; please refer to the Diesel Manual for further details. 7. If the outside ambient temperature is low, consider using a hot start. 8. Once the fault is eliminated, press the “RESET” key to reset.
  • J
    James Swanson PhDAug 22, 2025
    What to do if high temperature leads to diesel stop in Harsen GU320a Controller?
    • S
      simmonsanneAug 22, 2025
      If high temperature causes the diesel to stop, consider the following: 1. Check the temperature sensor mode of controller “T-sensor mode” for incorrect settings and reset if needed. 2. Check the diesel for overloading. 3. Inspect the radiator for blockages. 4. Check the fan belt for looseness. 5. Confirm that the outside temperature is within the generator's design range. 6. After the diesel cools down, check the cooling water level, but avoid adding a large amount of water at once. 7. Please refer to the Diesel Manual for further details. 8. Once the fault is eliminated, press the “RESET” key to reset. 9. In the condition of unload, keep the generator running for 10 minutes. After the “Genset” cooling down, on load again.
  • D
    Darin LewisAug 26, 2025
    What to do if low oil pressure leads to stop in Harsen GU320a?
    • D
      ddonaldsonAug 26, 2025
      If low oil pressure leads to a stop, take these steps: 1. Check the temperature sensor mode of controller “T-sensor mode” for incorrect settings; reset if needed. 2. Check the oil fuel level and add more if it is low. 3. Please refer to the Diesel Manual for further details. 4. Check the oil pressure switch with a testing instrument and replace it if it is faulty. 5. Once the fault is eliminated, press the “RESET” key to reset.
  • D
    Douglas ShortAug 28, 2025
    What causes over speed leading to diesel stop in Harsen GU320a Controller?
    • C
      Christopher ShawAug 28, 2025
      If over speed causes the diesel to stop, check the following: 1. Verify the temperature sensor mode of controller “H-sensor mode” and reset if it is incorrectly set. 2. Check the actuator for throttle lever movement and readjust if necessary. 3. If an electro-magnetic actuator is installed, check the throttle level for unhindered movement and adjust if needed. 4. Please refer to the Diesel Manual for further details. 5. Once the fault is eliminated, press the “RESET” key to reset.
  • J
    joehicksAug 31, 2025
    What to do if not enough speed leads to stop in Harsen GU320a?
    • R
      robert41Aug 31, 2025
      If not enough speed leads to a stop, consider the following: 1. Check the frequency entry of the controller speed sensor, reset if required. 2. Check the fuel level to ensure it is sufficient. 3. Check the actuator to see if it is removed; adjust if necessary. 4. If the electro-magnetic actuator has a throttle lever, check for unhindered movement and adjust if needed. 5. Adjust the diesel speed while it is running. 6. Please refer to the Diesel Manual for further details.
  • W
    William BarberSep 4, 2025
    Why does low voltage lead to stop in Harsen GU320a Controller?
    • M
      morenoscottSep 4, 2025
      If low voltage leads to a stop: 1. Reduce the load on the AC generator. After the generator stops, fix the fault and reset the “Genset”. 2. Check the “low voltage fault setting value” of “Main” to ensure the data is correct. 3. If the voltage is low, adjust the potentiometer to adjust the generator's output voltage to return to normal. 4. Please refer to the Alternator Manual for further details.
  • J
    Jennifer HoustonSep 7, 2025
    What causes high voltage leading to stop in Harsen GU320a Controller?
    • L
      Lindsay WillisSep 7, 2025
      If high voltage causes a stop: 1. Reduce the load on the AC generator. After the generator stops, fix the fault and reset the “Genset”. 2. Check the “high voltage fault setting value” of “Main” to ensure the data is correct. 3. Check the controller's measuring voltage; if it is normal, check the load to confirm it is non-capacitive. 4. If the voltage is high, adjust the potentiometer to adjust the generator's output voltage to return to normal. 5. Please refer to the Alternator Manual for further details.
  • J
    jeanette91Sep 12, 2025
    How to fix a Harsen Controller when generator fail to stop?
    • P
      pstewartSep 12, 2025
      If the generator fails to stop: 1. Check the fuel magnetic valve or throttle lever to ensure the fuel magnetic valve closes the oil channel safely in the closed condition. 2. Check the fuel magnetic valve and replace it if necessary.

Summary

Shape and Connection

Connection Port

Details of pin assignments, functions, signals, and line types.

Typical Wiring Diagram

Illustrates the general wiring connections for the controller.

Operation Panel

Installation

Control and Operation

Configuration for Operating Mode

Explains how to set the controller to AUTO, MAN, or TEST modes.

Start and Control Process

Details the sequence of starting and controlling the generator.

Fail to Start and Restart Condition

Describes conditions and procedures for start failures and restarts.

Measuring

Fault Signal

Stop Fault

Explains critical faults that stop the generator and require reset.

Parameter Configuration

Communication

Preparations

Troubleshooting

Startup Failures

Fault elimination steps for startup issues in MAN/AUTO modes.

Engine Operation Faults

Addresses diesel start failures, over/under speed, and temp/pressure issues.

Voltage Faults

Resolves generator stops due to low or high voltage conditions.

Failure to Stop

Steps to resolve issues where the generator fails to stop.

Harsen GU320a Specifications

General IconGeneral
BrandHarsen
ModelGU320a
CategoryController
LanguageEnglish

Related product manuals