EasyManua.ls Logo

Haskris R Series - Section 10: Cleaning an Air-Cooled Condenser; Air-Cooled Condenser Cleaning; Section 11: Maintenance Checks; General Maintenance Checks

Default Icon
11 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Copyright © 2020 Haskris REV102920
10
www.haskris.com
776 North Oaklawn Avenue, Elmhurst, Illinois 60126 USA ph: +1-847-956-6420 | fx: +1-847-956-6595 | email: service@haskris.com
Operation and Maintenance
Haskris LX-Series, R-Series, WW-Series, OPC-Series
Section 10: Cleaning an Air-Cooled Condenser
Air-cooled units collect dust and debris in the condenser during normal operation.
Accumulated debris restricts air ow and reduces heat transfer which reduces the capacity
of the unit.
To remove debris, turn the unit OFF and use a vacuum to collect the debris.
See Figure 3 and 4.
Use a brush to loosen compacted debris.
Section 11: Maintenance Checks
Inspect the water (if applicable) in the tank. Make sure it is clean and the level is proper. (see
Section 6 or Section 7)
Perform a system ush or line ush if you observe signicant accumulation of debris or biological
growth. (see Section 6.2)
Inspect and clean or replace strainers and lters. (see Section 3, Section 4, Section 7.3)
Clean air-cooled condenser coils and ns if necessary. (see Section 10)
Fig. 3
Fig. 4
Section 11.1: Schedule for Maintenance Checks
After a new installation, perform these checks at least every 2 weeks for 3 months
Beyond 3 months, perform checks at least 1 or 2 times per year.