EasyManua.ls Logo

Haskris R Series - Page 3

Default Icon
11 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Copyright © 2020 Haskris REV102920
3
www.haskris.com
776 North Oaklawn Avenue, Elmhurst, Illinois 60126 USA ph: +1-847-956-6420 | fx: +1-847-956-6595 | email: service@haskris.com
Operation and Maintenance
Haskris LX-Series, R-Series, WW-Series, OPC-Series
Section 1.2: Parametric Control
Refrigeration runs continuously to maintain steady supply uid temperature under a steady heat load and steady ambient conditions.
Non-refrigerated units use a facility water regulating valve to maintain steady supply uid temperature under a steady heat load.
The LEDs labeled PV display the present value of the uid temperature.
The LEDs labeled SV display the set point value.
Set Point Adjustment
1. Press the UP and DOWN arrows to adjust set
point value.
High/Low Temperature Alarm Adjustment
Alarm set points depend on the
application specications and unit
design. Contact Haskris to conrm
factory settings.
1. Press the button once. PV displays
A1.SP. SV displays an alarm set point.
2. Before adjusting the alarm set point, record the
original setting. Press the UP and DOWN arrows
to adjust the alarm set point.
3. Press the button again. PV may display
A2.SP. If the setting is not used or not adjustable,
A2.SP will not appear. Adjust if necessary.
4. Press the button to return to the normal
temperature display.

Related product manuals