RESETTING MEMORY TO FACTORY VALUES:
If some portions of the memory have been "corrupted" you should consider resetting
to the factory default values and then changing any specific values you need to. This insures
a "clean slate" for your new set up.
1) Follow the procedure outlined on the previous page to first reset the
microprocessor.
2) Select Battery bank #1 on the LINK 2000 to reset to factory values for Battery #1.
To also reset Inverter and Charger functions to factory defaults be sure that the
INVERT and CHARGE LEDs are lit.
3) Press and hold the SET UP button for approximately 10 seconds. After 5
seconds the SET UP LED will begin to flash slowly, continue to hold until the
SET UP LED begins to flash quickly (about 3 times per second). Release the
SET UP button,
press and hold the RESET A HRS button ( blue legend under
BATTERY #1 button). After holding down the RESET A HRS button for
about 5 seconds you should see a 0 (zero) appear in the display momentarily.
If you do not see the zero, the meter did not reset and this step must be
repeated.
4) Select Battery bank #2 on the LINK 2000 to reset to factory values for Battery #2.
5) Repeat step 3.
6) Re-program the necessary set up values such as battery type, capacity, ambient
temperature, Peukert's exponent, Inverter/Charger parameters, etc..