Operation Timer Defrost auto Outdoor
LED LED LED LED
LED(RED)
XXX
XXX
XX X
XX
XX
XXX
XXX
OFF
XXX
Flash at 5Hz X OFF
SMASMH1824SA
AUTOTIMERPREDEF.OPERATIO
N
Flashes
5 CommunicationFailure
2 CondensorTemperatureSensor
1 OtherIndoorFailure
SMASMH1824SB
SMA/SMH18‐24DIAGNOSTICS
Indoor unit communication error
EEROM error
outdoor unit protects (outdoor temp thermister,phase order ect.)
(without for cooling only models)
Outdoor condenser temperature thermister is open or shorted
Indoor evaporator thermister is open or shorted
Indoor room thermister is open or shorted
over current protection of the compressor occurs 4 times
FailureMode
OutdoorUnitDiagnostic
Outdoor led should be solid RED for normal operation
no voltage outdoor transformer
UNPLUGGED(S)WIRE(LOCKOUT35MINUTES
)
AUTOPREDEF.OPERATIONTIMER
OVERCURRENT‐CHECKVOLTAGE‐LOWVOLTAGE‐HIGHAMP
S
VOLTAGESHOULDBEBETWEEN175‐253VOLT
S
OUTDOORUNITPROTECTS‐CHECKPOWERSUPPL
Y
COULDBETHEOUTDOORPCBORTHECOMPRESSORONLOCKEDROTOR
COMMUNICATIONERROR‐L1&2NREVERSED fromtheindoortotheoutdoo
r
AUTO(GREENLED)FLASHESATTHEEVAP.&(RED LED)FLASHESFIVE
TIMESINTHEOUTDOORUNIT.ITTAKES23MINUTESFORTHE
UNITTOREACTANDSTARTFLASHING
WHENTHEPOWERISAPPLIEDTOTHEOUTDOORUNITTHERED LED
TURNSSOLIDREDIFTHE(S)WIREISDISCONECTED
ORANYFAULTSWITHTHE
EVAPORATORTHEREDLEDFROMTHEOUTDOORUNITFLASHESFIVETIMES
OUTDOORUNITTRANSFORMERVOLTAGE230TO12VA
C
VOLTAGEFROM2(N)TO(S)TOTHEEVAPORATOR12VOLTD
NO12VOLTAGEFROMTHETRANSFORMER2(N)TO(S)YOUGET32VD
C
FROM2(N)TO(S)ANDTHEAUTOGREENLEDFLASHESAFTER23MINITE
S
THEOUTPUTVOLTAGEWILLVARYDEPENDINGONTHEINCOMINGVOLTAGE
8.8.