EasyManua.ls Logo

Heat Controller VMH09SC-1 - 8.4.2 Cooling Mode Operation

Heat Controller VMH09SC-1
45 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
22
Service Manual VMH SerieS Heat Controller, Inc.
21
8.4.2 Cooling Mode
8.4.2.1 Compressor running rules:
The operating frequency of compressor after starting submits to following rule.
If users switch on A/C by remote controller, the compressor will run at the Fmax frequency for 7 minutes
according to outdoor ambient temp. During the 7 minutes, frequency limitation is active.
7 minutes later, the compressor running frequency will be controlled as below:
While
Temp. zone
A
B
C
D
E
F
G
Frequency
F8
F8
F7
F6
F5
F3
F1
T4
°F °C
113 (45)
109 (43)
104 (40)
100 (38)
86 (30)
82 (28)
72 (22)
68 (20)
T1-Ts
°F °C
38 (3.5)
37 (3.0)
37 (2.5)
36 (2.0)
40 (1.5)
34 (1.0)
33 (0.5)
29 (-0.5)
30 (-1.0)

Related product manuals