43
Heat Controller, Inc. VMH SerieS Service Manual
42
8.3.1. Compressor checking (Model: DA150S1C-20FZ)
Measure the resistance value of each winding by using the multi-meter.
Outdoor Fan Motor (Model: YDK53-6FB)
Measure the resistance value of each winding by using the multi-meter.
Outdoor Fan Motor (Model: YDK53-6NB)
Measure the resistance value of each winding by using the multi-meter.
Position Resistance
Value
Blue - Red
0.95Ω
(20
)
Blue - Black
Red - Blue
Position Resistance
Value
Black - Red
56Ω (20
)
Red -Yellow 76Ω (20
)
Position Resistance
Value
Black - Red
56.5Ω (20
)
Red -Yellow 117.5Ω (20
)