7 Error Handling
48 Programmer PG 02
Cause: No data found or check sum over data is wrong.
Response: - Engine cannot be started.
- Governor is operating by default parameters.
Action: - Check data for correct setting, save parameters and restart control unit by a
reset.
Note: This error will occur only when adjusting and saving parameters.
3091 ErrLogical 3191 SErrLogical
Cause: Error of data structure.
Response: - Control cannot be started.
- Governor is operating by default parameters.
Action: - Check data for correct setting, restart governor by a reset.
- Notify HEINZMANN.
3093 ErrStack 3193 SErrStack
Cause: Internal programming or computing error, “stack-overflow”.
Response: - Control cannot be started.
- Emergency shutdown.
Action: - Write down the value of parameter 3897 StackTestFreeBytes and notify
HEINZMANN
- Restart control by a reset.
3094 ErrIntern 3194 SErrIntern
3095 ExceptionNumber 3195 SExceptionNumber
3096 ExceptionAddr1High 3196 SExceptionAddr1High
3097 ExceptionAddr1Low 3197 SExceptionAddr1Low
3098 ExceptionAddr2High 3198 SExceptionAddr2High
3099 ExceptionAddr2Low 3199 SExceptionAddr2Low
Cause: Internal programming or computing error, so-called "EXCEPTION" error.
Response: - Control cannot be started.
- Emergency shutdown.
Action: - Write down the values of the parameters 3095 ExceptionNumber,
3096 ExceptionAddr1High, 3097 ExceptionAddr1Low,
3098 ExceptionAddr2High and 3099 ExceptionAddr2Low and
notify HEINZMANN.
- Restart control by a reset.