7 Error Handling
Programmer PG 02 47
- Restart governor by a reset.
- Notify HEINZMANN.
3085 ErrVoltage 3185 SErrVoltage
Cause: The supply voltage for the governor is not within the permissible range from
18 to 33V.
Response: - Error message.
- Error is cleared automatically as soon as the voltage is back within the
normal range.
Action: - Check voltage supply.
3087 ErrCPU 2 3176 SErrCPU2
Cause: CPU 2 is out of order.
Response: - Error message.
Action: - Notify HEINZMANN.
Note: These parameters are implemented only in the PRIAMOS series.
3087 ErrMainCheckSum
Cause: Check-sum of control programme is wrong.
Response: - Governor cannot be put into operation.
Action: - Restart governor by a reset.
- Notify HEINZMANN.
Note: This error will only be displayed by the bootloader.
3089 ErrWatchdog
Cause: Internal computing error, so-called “Watchdog Error”.
Response: - Governor cannot be put into operation.
- Emergency shutdown.
Action: - Restart governor by a reset.
- Notify HEINZMANN.
Note: This error will only be displayed by the bootloader.
3090 ErrData 3190 SErrData