7 Error Handling
46 Programmer PG 02
3071 ErrCanComm 3171 SErrCanComm
Cause: There is an overrun in the destination buffer or a message cannot be fed into
CAN bus.
Response: - Depending on the application.
Action: - Check CAN module.
- Check CAN connection.
3075 ErrClearFlash 3175 SErrClearFlash
Cause: Occurrence of an error on clearing the control's flash memory.
Response: - Control cannot be put into operation.
- Emergency shutdown.
Action: - Restart governor by a reset.
- Notify HEINZMANN.
3076 ErrParamStore 3176 SErrParamStore
Cause: Occurrence of an error on programming the control's flash memory.
Response: - Control cannot be put into operation.
- Emergency shutdown.
Action: - Restart governor by a reset.
- Notify HEINZMANN.
3077 ErrProgramTest 3177 SErrProgramTest
Cause: Current monitoring of the programme memory reports an error.
Response: - Engine cannot be started.
- Emergency shutdown.
Action: - Restart governor by a reset.
- Notify HEINZMANN.
3078 ErrRAMTest 3178 SErrRAMTest
Cause: Current monitoring of the working memory reports an error.
Response: - Engine cannot be started.
- Emergency shutdown.
Action: - Note down the values of the parameters 3895 RAMTestAddrHigh and
3896 RAMTestAddrLow.