Error Code List
© 2009 Hirschmann Automation and Control GmbH · Branch Office Ettlingen · eMail: info.ecs@hirschmann.de · www.hirschmann.com 22
24 183 69 1012e (Generic) / 2009-02-26 / Rev. 01 / rk.
Error Code Error Cause Elimination
E32
Error in the power
supply
+UB System not present at the
system start
+UB System not present at the
system finish
Contact problems at +UB
switch off/on
+UB System and +UB Power
must be wired separately: +UB
System connected direct with
the crane battery. +UB Power
for switch on/off
+UB switch off/on again
E37
Error in the logical
program flow
System program file is
defective
Flash-EPROM defective
Upload valid system software
Replace central unit
E38
System program and
crane data file do not
match.
The system program in the LMI
does not match to the
programming in the crane data
file
Upload valid system program
file or the valid crane data file
E39
System program and
load chart file do not
match
The system program in the LMI
and the programming in the
load chart file do not match.
Upload valid system program
file or the valid load chart file
E43
Error in the write/read
memory, (RAM)
Write/read memory (RAM) or
central unit defective.
Replace central unit
E47
Error in the monitored
write/ read memory.
The CRC verification of
the monitored write/read
memory provides an
incoherent result
The CRC sign of the monitored
write/read memory is wrong
The buffer battery is decharged
(< 2V at 1kOhm).
Central unit defective.
Restart the LMI
Replace buffer battery on the
central unit.
Replace central unit
E51
Error in the crane data
file
No valid data in the crane data
file.
Flash-EPROM defective
Upload valid crane data file
Replace central unit
E52
Error in load chart file.
No valid data in the load chart
file
Flash-EPROM defective
Upload valid load chart file
Replace central unit
E53
Wrong setup of min.
analog inputs length1,
angle1, pressure1
Analog input not supported Setup correct Flag in in DGA
6.i.2
E56
Error in crane data file.
No valid data in the crane data
file during calibration.
Flash-EPROM defective
Restore or upload valid crane
data file
Replace central unit
E57
Error in serial crane
data file.
Calibration data file does not
contain valid data.
Flash-EPROM defective
Upload calibration data file by
changing data (OM, limits) and
save
Replace central unit
CAN Bus cable between the
central unit and the sensor unit
defective or not connected.
Check the connection between
the central unit and the sensor
units
E61
Error in the CAN bus
data transfer for all CAN
units
Can bus port in the central unit
defective
Replace the central unit